![Senlan SB200 Series Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/senlan/sb200-series/sb200-series_user-manual_1239807041.webp)
Lists of function parameters
37
F2: V/F Control Parameters
Paramete
r
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
F2-00
V/F Curve Settings
0: Custom
1: Linear
2: V/F Curve 1 (Torque lowering)
3: V/F Curve 2 (Torque lowering) 4: V/F
Curve 3 (Torque lowering)
5: V/F Curve 4 (Torque lowering) 6: V/F
Curve 5 (Torque lowering)
1
×
88
F2-01
Torque Elevation
Options
0: Inapplicable
1: Manual elevation
2: Auto elevation
3: Manual ele auto elevation
1
×
88
F2-02
Amplitude of Manual
Torque Elevation
0.0%—the max. value depends on inverter
model number; min. unit: 0.1%
Depend on
inverter
model No.
○
89
F2-03
Cut-Off Point of Manual
Torque Elevation
0.0—100.0%; F2-12 is taken as 100%
10.0%
○
89
F2-04
Auto Torque Elevation
Range
0.0—100.0%
100.0%
×
89
F2-05
Slip Compensation Gain
0.0—300.0%
0.0%
○
90
F2-06
Filter Time of Slip
Compensation
0.1—25.0s
1.0s
×
90
F2-07
Clipping of Electric Slip
Compensation
0—250%; The rated slip frequency of the
motor is taken as 100%
200%
×
90
F2-08
Clipping of Regenerated
Slip Compensation
0—250%; The rated slip frequency of the
motor is taken as 100%
200%
×
90
F2-09
Vibration Dampening
0—200
Depend on
inverter
model No.
○
91
F2-10
AVR Settings
0: Inapplicable
1: Always applicable
2: Only inapplicable in deceleration
1
×
91
F2-11
Auto Energy-Saving
Options
0: Inapplicable
1: Applicable
0
○
92
F2-12
Basic Frequency
1.00—650.00Hz
50.00Hz
×
92
F2-13
Max. Output Voltage
150—500V
380V
×
92
F2-14
V/F Frequency F4
F2-16—F2-12
0.00Hz
×
92
F2-15
V/F Voltage V4
F2-17—100.0%;
F2-13 is taken as 100%
0.0%
×
92
F2-16
V/F Frequency F3
F2-18—F2-14
0.00Hz
×
93
F2-17
V/F Voltage V3
F2-19—F2-15;
F2-13 is taken as 100%
0.0%
×
93
F2-18
V/F Frequency F2
F2-20—F2-16
0.00Hz
×
93
F2-19
V/F Voltage V2
F2-21—
~
F2-17;
F2-13 is taken as 100%
0.0%
×
93
F2-20
V/F Frequency F1
0.00Hz—F2-18
0.00Hz
×
93