![Senlan SB200 Series Скачать руководство пользователя страница 155](http://html1.mh-extra.com/html/senlan/sb200-series/sb200-series_user-manual_1239807155.webp)
Solutions to Faults and Abnormalities
151
7 Solutions to Faults and Abnormalities
7.1 Inverter Faults and Solutions
List of Fault Description and Solutions
Fault Display
(Fault Code)
Fault Type
Possible Cause
Solution
The interior or wiring of the
motor has an inter-phase short
circuit or short circuit to earth
Check the motor and wiring
The inversion module is
damaged
Seek for assistance
Er.ocb (1)
Instantaneous
Startup
Overcurrent
The voltage is too high at the
outset of the startup
Check the torque elevation
settings
The acceleration time is too
short
Extend the acceleration time
The V/F curve is inappropriate Adjust the V/F curve or the
torque elevation settings
An operating motor is
restarted
Set the motor as rotation speed
tracking startup
Do not restart until the motor is
shut down
The power grid has a low
voltage
Check the power supply
Er.ocA (2)
Accelerated
Operation
Overcurrent
The inverter power is too low
Replace it with a inverter of
greater ratings
The deceleration time is too
short
Extend the deceleration time
There is a potential energy
load or the inertia torque of
the load is too great
Fit the inverter with an
appropriate dynamic braking
units
Er.ocd (3)
Decelerated
Operation
Overcurrent
The inverter power is too low Select a inverter of greater
power ratings
Load surge
Reduce the load surge
Abnormal load
Check the load
The power grid has a low
voltage
Check the power supply
The inverter power is too low Select a inverter of greater
power ratings
Er.ocn (4)
Constant Speed
Operation
Overcurrent
Abnormal input voltage
Check the power supply
An operating motor is
restarted
Set the motor as rotation speed
tracking startup
Do not restart until the motor is
shut down
Er.ouA (5)
Accelerated
Operation
Overvoltage
The deceleration time is too
short
Extend the deceleration time