Details about Function Parameters
138
The units are effective only for the LCD panel and are used to display the units of parameters.
6.13 FF: Communication Parameters
FF-00
Communication Protocol Options
Factory
Settings
0
Modification
×
Setting
Range
0: Modbus protocol 1: Compatible USS commands 2: CAN bus
FF-01
Communication Data Format
Factory
Settings
0
Modification
×
Setting
Range
0: 8,N,1 (1 start bit; 8 data bits; no parity check; 1 stop bit)
1: 8,E,1 (1 start bit; 8 data bits; even parity check; 1 stop bit)
2: 8,O,1 (1 start bit, 8 data bits; odd parity check; 1 stop bit)
3: 8,N,2 (1 start bit, 8 data bits; no parity check; 2 stop bits)
FF-02
Baud Rate Options
Factory
Settings
3
Modification
×
Setting
Range
0: 1200bps 1: 2400bps 2: 4800bps 3: 9600bps
4: 19200bps 5: 38400bps 6: 57600bps 7: 115200bps
8: 250000bps 9: 500000bps
NOTE: 0
~
5 are for Modbus and compatible USS command protocols; 0
~
9 are for
CAN bus.
FF-03
Local IP Address
Factory
Settings
1
Modification
×
Setting
Range
0
~
247
NOTE: 1
~
247 are for Modbus; 0
~
31 are for compatible USS commands; 0
~
127 are
for CAN bus
FF-04
Communication Timeout Detection
Time
Factory
Settings
10
.0
s
Modification
○
Setting
Range
0.1
~
600.0s
FF-05
Local Response Delay
Factory
Settings
5
m
s
Modification
○
Setting
Range
0
~
1000ms
FF-06
Communication Timeout Action
Factory
Settings
0
Modification
×
Setting
Range
0: No action 1: Alarm 2: Fault and free shutdown
3: Alarm; press F0-00 for operation
4: Alarm; press F0-07 for operation at an upper limit frequency
5: Alarm; press F0-08 for operation at the lower limit frequency
FF-07
USS Message PZD Words
Factory
Settings
2
Modification
×
Setting
Range
0
~
4