Lists of function parameters
55
Paramete
r
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
protection
0: No action 1: alarm 2: fault and free
shutdown
Thousands digit: Parameter storage failure
action options
0: Alarm 1: Fault and free shutdown
Fb-12
Acceleration
Overcurrent Stall
Prevention Options
0: Invalid
1: Valid; Abnormal shutdown will be
reported in the event of a stall timetout
(Er.Abb)
2: Valid; No time limit is set for stall
1
×
148
Fb-13
Acceleration
Overcurrent Stall Point
10.0
~
130.0%; the rated inverter current is
taken as 100%
110.0%
×
148
Fb-14
Constant Speed
Overcurrent Stall
Prevention Options
0: Invalid
1: Valid; Abnormal shutdown will be
reported in the event of a stall timetout
(Er.Abb)
2: Valid; No time limit is set for stall
1 ×
148
Fb-15
Constant
Speed Overcurrent
Stall Point
10.0
~
110.0%; the rated inverter current is
taken as 100%
110.0% × 149
Fb-16
Overvoltage Stall
Prevention Options
0: Invalid 1: Valid
1
×
149
Fb-17
Overvoltage Stall Point
650
~
750V
700V
×
149
Fb-18
DC Busbar Undervotage
Action
0: Free shutdown; an undervoltage fault is
reported (Er.dcL)
1: Free shutdown; the time-limited power
supply is restored and restarted
2: Free shutdown; the power supply is restored
and restarted while the CPU is in operation
3: Decelerated operation; busbar voltage is
maintained
0 ×
150
Fb-19
DC Busbar Undervoltage
Point
300
~
450V
380V ×
150
Fb-20
Instantaneous Power
Failure Time Allowance
0.0
~
30.0s
0.1s
×
150
Fb-21
Instantaneous Power
Failure Deceleration
Time
0.0
~
200.0s; if the value is set as 0.0, the
present deceleration time is adopted
0.0s
×
150
Fb-22
Fault Self-Reset
Frequency
0
~
10; Module protection and external fault
protection are not complete with the self-reset
function.
0 ×
151
Fb-23 Self-Reset
Interval 1.0
~
30.0s
5.0s ×
151
Fb-24
Fault Output during
Self-Reset
0: Output applicable
1: Output inapplicable
0 ×
151
Fb-25
Restart Mode of
Instantaneous Power
0: Startup in the startup mode
1: Tracking startup
1
×
151