Details about Function Parameters
101
%
F6-00 =
-
100.00
Min. Input Analog Quantity
F6-01 = 100.00
Max. Input Analog Quantity
F6-02 = 0.00
Settings/feedback value corresponding with min. input analog quantity
F6-03 = 100.00
Settings/feedback value corresponding with max. input analog quantity
F6-04 =
-
100.00
Input Analog Quantity of Inflection Point
F6-05 = 0.00
Deviation from inflection point
F6-06 = 0.00
Settings/feedback value corresponding with inflection point
10V/20mA V/mA
100%
(F6-01,F6-03)
(F6-00,F6-02)
(F6-04,F6-02)
0
-10V/-20mA
Analog Input Example 5 (Reversed polarity application):
In some applications where the analog input voltage is 0
~
10V/0
~
20mA in correspondence with the
set value/feedback value of 100
~
0
%
, the parameter settings will be as follows. At this point, the input
analog quantity at inflection point overlaps the min. analog input quantity.
Analog Input Example 6 (Application with inflection point):
In some application where the analog input voltage is -10
~
10V/-20
~
20mA in correspondence with
the set value/feedback value of -100
~
100
%
, the parameter settings will be as follows. In this case,
when the analog input is used for frequency settings, the rotation direction of the motor will depend on
the positive/negative feature of the input quantity. The inflection point settings are used for deadband
settings in clockwise/anticlockwise rotation
Analog Input Example 7 (Application with inflection point):
In some applications where the analog input voltage is 0
~
10V/0
~
20mA (split into two slope rates),
the parameter settings will be as follows.
%
10V/20mA V/mA
100%
(F6-01,F6-03)
(F6-00,F6-02)
(F6-04,F6-06)
F6-00 = 0.00
Min. Input Analog Quantity
F6-01 = 100.00
Max. Input Analog Quantity
F6-02 = 20.00
Settings/feedback value corresponding with min. input analog quantity
F6-03 = 100.00
Settings/feedback value corresponding with max. input analog quantity
F6-04 = 0.00
Input Analog Quantity of Inflection Point
F6-05 = 0.00
Deviation from inflection point
F6-06 = 20.00
Settings/feedback value corresponding with inflection point
0
%
10V/20mA V/mA
100%
(F6-01,F6-03)
(F6-00,F6-02)
F6-00 =
-
100.00
F6-01 = 100.00
F6-02 =
-
100.00
F6-03 = 100.00
F6-04 = 0.00
F6-05 = 5.00
F6-06 = 0.00
0
-10V/-20mA
-100%
F6-05
F6-04
Min. Input Analog Quantity
Max. Input Analog Quantity
Settings/feedback value corresponding with min. input analog quantity
Settings/feedback value corresponding with max. input analog quantity
Input Analog Quantity of Inflection Point
Deviation from inflection point
Settings/feedback value corresponding with inflection point