Details about Function Parameters
132
Fault Self-Reset:
Faults in operation will be self-reset according to Fb-23 “Self-Reset Interval”
and Fb-22 “Fault Self-Reset Frequency”. Restarts will also be possible. This function is intended
to prevent trips caused by misoperation, instantaneous overvoltage of the power supply or
external non-repetitive impacts.
Self-Reset:
Faults in operation will be self-reset after the self-reset interval. If the fault is
corrected, press Fb-25 “Restart Mode of Instantaneous Power Failure, Self-Reset and Operation
Suspension” for a restart. If the fault persists and the reset frequency has not exceeded Fb-22,
self-reset trials will continue; otherwise, a fault will be reported and the system will shut down.
Zero Clearing Conditions of Fault Reset Frequency:
After the inverter has a fault self-reset,
no fault will follow in 10 minutes on end. If the fault is detected, manual reset will be needed.
The power supply will be resumed after power failure.
Fb-24 “Fault Output during Self-Reset”: During the self-reset, Digital Output 6 “Fault Output”
can be tested if it is effective.
Power device protection (Er.FoP) and external faults (Er.EEF) will not require a self-reset.
CAUTION: Self reset must be used with care; otherwise personal injuries or property
losses may occur.
Fb-26
Poweron Self-Restart Enabled
Factory
Settings
1
Modification
○
Setting
Range
0: Disabled 1: Enabled
In the case of a terminal execution command channel where a level-type working mode is
selected (F4-13
=
0, 1 or 2), if the execution command becomes effective upon power supply.
You may choose if the parameter selection will cause a prompt startup upon power supply.
Fb-27
Braking Unit Working Point
Factory
Settings
680V
Modification
○
Setting
Range
620
~
720V
The braking resistor of a braking unit will consume energy to realize a quick shutdown. If the DC
busbar voltage exceeds the braking unit working point, the braking unit will automatically start
up.
This parameter only applies to inverter types with inbuilt braking units.
Fb-28
Modulation Mode
Factory
Settings
0
Modification
○