Installation and Wiring
20
The control cable, power cable and motor cable must be kept apart in order to prevent intercoupling
interference. The three types of cable must be spaced at a sufficiently wide distance, especially when
they are installed parallel to each other and run for a relatively long distance. Whenever the signal cable
has to cross over the power cable, they must be vertical to each other. Refer to the following drawings:
The bigger the length and the cross section of the motor cable, the bigger the capacitance to earth and
the interference caused by intercoupling. Therefore, cables of a specified cross section and of an
appropriately minimized length are recommended.
The following drawings specify earthing modes recommended for the wiring:
Inverter
Other
equipment
Inverter
Other
equipment
Separately earthed
(Preferred)
Jointly earthed
(Acceptable)
The following earthing modes are not allowed:
Inverter
Other
equipment
Other
equipment
Inverter
3.3.2. Terminal, Jumper and Wiring of Control Panel
Refer to the following table for the functions of jumpers on the control panel:
Code
Name
Function and Configuration
Factory
Setting
CJ1 AI1 Input Type Options: V: Voltage mode; mA: Current mode
V