Lists of function parameters
35
Para
meter
Name
Setting Range and Description
Factory
Settings
Modifi
cation
Pag
e
F0-11
Parameter
Initialization
11: Initialization
22: Initialization applicable to all parameters but
communication parameters
00
×
80
F0-12
Parameter
Copying
(Applicable to
SB-PU70E and
SB-PU200
11: Parameters are uploaded from the inverter to the
panel
22: Parameters are downloaded from the panel to the
inverter
33: Verifies the unconformity of panel settings to
inverter parameters
44: Clears parameters stored in the panel
00
×
81
F0-13
Rated Inverter
Power
Min. unit: 0.01kW
Depend on
inverter
model
△
81
F0-14
Software Version
No.
0.00—99.99
Depend on
version
△
81
F0-15
User Password
Settings
0000—9999; “0000” means no password has been
set
0000
○
81
F1: Acceleration/Deceleration, Startup, Shutdown and Jog Parameters
Parameter
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
F1-00
Acceleration Time 1
82
F1-01
Deceleration Time 1
82
F1-02
Acceleration Time 2
82
F1-03
Deceleration Time 2
0.1—3600.0s
Acceleration Time: The time required for the
frequency to increase by 50Hz
Deceleration Time: The time required for the
frequency to decrease by 50Hz
NOTE: Factory settings for 22kW inverters
and below are 6.0s
Factory settings for 30 kW inverters and above
are 20.0s
Depend on
inverter
model No.
○
82
F1-04
Deceleration Time
in an Emergency
Shutdown
0.1—3600.0s
10.0s
○
82
F1-05
Auto Switching
Point for
Acceleration/Decele
ration Time
0.00—650.00Hz; Below this range is
Acceleration/Deceleration Time 2
0.00Hz
×
82
F1-06
Jog Frequency
0.10—50.00Hz
5.00Hz
○
84
F1-07
Jog Acceleration
Time
0.1—60.0s
Depend on
inverter
model No.
○
84
F1-08
Jog Deceleration
Time
0.1—60.0s
Depend on
inverter
model No.
○
84
F1-09
Clockwise/Anticloc
kwise Rotation
Deadband Time
0.0—3,600.0s
0.0s
×
84