Details about Function Parameters
148
FP-17
Type of Last but Four Fault
Min.
Unit
1
Modification
△
FP-18
Cumulative Operation Time during Last
but Four Time
Min.
Unit
1h
Modification
△
FP-19
Single Operation Time during a Fault
Min.
Unit
0.1h
Modification
△
FP-20
Fault List Cleared
Min.
Unit
1
Modification
○
Setting
Range
11: Clear the parameters in this menu and they will change automatically into 00 upon
completion of the operation
Refer to the follow list of inverter faults
0: No fault
1.ocb: Instantaneous startup
overcurrent
2.ocA: Accelerated operation
overcurrent
3.ocd: Decelerated operation
overcurren
4.ocn: Constant speed operation
overcurrent
5.ouA: Accelerated operation
overvoltage
6.oud: Decelerated operation
overvoltage
7.oun: Constant speed operation
overvoltage
8.ouE: Overvoltage on standby
11.PLo: Output phase lack
12.FoP: Power device protection
13.oHI: Inverter overheat
14.oLI: Inverter overload
15.oLL: Motor overload
16.EEF: External fault
17.oLP: Motor overload
18.ULd: Inverter underload
19.cnF: Main loop contactor fault
20.cno: Water supply system
contactor fault
21.EEP: Parameter storage failure
22.CFE: Communication
abnormality
23.ccF: Current detection fault
24. LPo: Water level transducer
abnormality
25.Aco: Analog input offline
26.PLL: Clean water pool water
shortage
27.rHo: Thermal resistor
open-circuit
28.Abb: Abnormal shutdown fault
29: Retained
30: Retained
31.PnL: Control panel offline