Lists of function parameters
44
Paramete
r
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
F6-00
AI1 Min. Input
Analog Quantity
0.00%
○
113
F6-01
AI1 Max. Input Analog
Quantity
-100.00
-
100.00%
100.00%
○
113
F6-02
Set Value/Feedback
Value Corresponding
with AI1 Min. Input
Analog Quantity
0.00%
○
114
F6-03
Set Value/Feedback
Value Corresponding
with AI1 Max. Input
Analog Quantity
-100.00
-
100.00%
NOTE: Frequency settings must be based on the
max. frequency as a reference; the PID set
value/feedback value must be represented as the
percentage of the PID reference values
100.00%
○
114
F6-04
Input Analog Quantity of
AI1 Inflection Point
F6-00 “Min. Analog Quantity”—F6-01“Max.
Analog Quantity”
0.00%
○
114
F6-05
Deviation from AI1
Inflection Point
0.00—50.00% 2.00%
○
114
F6-06
Set Value/Feedback
Value Corresponding
with AI1 Inflection Point
-100.00
-
100.00%
0.00%
○
114
F6-07
AI1 Offline Threshold
-20.00
-
20.00%
0.00
○
114
F6-08
AI1 Input Filter Time
0.000
-
10.000s
0.100s
○
114
F6-09
AI2 Min. Input Analog
Quantity
20.00%
○
114
F6-10
AI2 Max. Input Analog
Quantity
-100.00
-
100.00%
100.0%
○
114
F6-11
Set Value/Feedback
Value Corresponding
with AI2 Min. Input
Analog Quantity
0.00%
○
115
F6-12
Set Value/Feedback
Value Corresponding
with AI2 Max. Input
Analog Quantity
-100.00
-
100.00%
NOTE: Frequency settings must be based on the
max. frequency as a reference; the PID set
value/feedback value must be represented as the
percentage of the PID reference values
100.00%
○
115
F6-13
Input Analog Quantity of
AI2 Inflection Point
F6-09 “min. analog quantity”
-
F6-10“maxium analog quantity”
20.00%
○
115
F6-14
Deviation from AI2
Inflection Point
0.00
-
50.00%
2.00%
○
115
F6-15
Set Value/Feedback
Value Corresponding
with AI2 Inflection Point
-100.00
-
100.00%
0.00%
○
115
F6-16
AI2 Offline Threshold
-20.00
-
20.00%
0.00
○
115
F6-17
AI2 Input Filter Time
0.000
-
10.000s
0.100s
○
115
F6-18
AI3 Min. Input Analog
Quantity
-100.00
-
100.00%
0.00%
○
115
F6-19
AI3 Max. Input Analog
Quantity
100.0%
○
115