3.14
SEL-2032
Communications Processor
Instruction Manual
Date Code 20120126
Job Done Examples
Example 3: Collect SEL Relay Status and Measurements
Step 2. Enter Access Level 2 on the SEL-2032 and issue the command
SET P 2
to configure Port 2.
The SEL-2032 prompts for the type of device connected to the
port.
➢
Enter
S
for SEL IED,
Y
to auto-configure the port, and
press the
<Enter>
key to confirm the configuration
prompts.
The SEL-2032 establishes communication with the
relay; determines the type of relay, relay ID, and
communication baud rate; and determines if the relay is
capable of Fast Meter.
➢
Enter
Y
to save port configuration changes at the final
prompt.
Step 3. Issue the
AUTO 2
command to see what Fast Message features
are supported by the SEL-351S.
shows an example
output for the
AUTO
command.
*>>
AUTO 2 <Enter>
FID: FID=SEL-351S-7-R106-V0-Z003003-D20010110
DEVICE ID: FEEDER 1
BAUD RATE: 19200
OPERATE SUPPORT: Binary (1 Breakers, 16 Remote Bits S-C-P)
LEVEL 1 PASSWORD: OTTER
COMMANDS SUPPORTED:
B 20METER
B 20DEMAND
B 20TARGET
A 20HISTORY
A 20STATUS
A 20EVENT
A 20EVENTS
A 20EVENTL
*>>
Figure 3.12
Example AUTO Command Output
Step 4. Next, issue the command
SET A 2
to set an auto-message to
collect relay meter and target data.
➢
Respond to prompts about saving unsolicited messages
(AUTOBUF), the STARTUP string, operate command
enable (
SENDOPER
), and receive SER enable
(
RECSER
).
➢
Press
<Enter>
to confirm the defaults for all of these.
➢
Enter
2
when prompted for the message count.
➢
At the ISSUE1 prompt, enter
P00:00:01
to set the
message to trigger once every second.
➢
At the MESG1 prompt, enter
20METER
to send the
request for meter data to the SEL relay.
➢
At the ISSUE2 prompt, enter
P00:00:01
and at the
MSG2 prompt enter
20TARGET
to collect relay target
data.
➢
Enter
END
and press
<Enter>
to accept the default for
remaining settings and enter
Y
to save changes.
As soon as the SEL-2032 accepts the setting change, the TXD
and RXD Port 2 LEDs on the SEL-2032 will begin to flash as
the SEL-2032 requests and receives meter data every second.
Содержание SEL-2032
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...