7.29
Date Code 20120126
Instruction Manual
SEL-2032 Communications Processor
Settings
User-Defined (SET U) Commands
WRITE,
and
TRANS
special purpose commands may be useful with master
devices that you can program to communicate automatically with the
SEL-2032.
To build these commands, you must specify the position and format of the port
number, address, and data, as applicable, within the message. You then specify
how the SEL-2032 should respond to each of these commands for both
successful and unsuccessful operations.
For example, assume you have made the following settings. See
for an explanation of the special characters used in these
settings.
TRANS = "TR\Pa/" TRANSACK = "\006" TRANSNACK = "\015"
To enter transparent
mode with another SEL-2032 port, use the message format you
defined with the
TRANS
command. For example, to enter transparent
mode with Port 5 with these settings, issue the command
TR05
<Enter>
. If the transparent connection is successful, the SEL-2032
responds with 06h (ASCII ACK) and you will be transparently
connected. To terminate the transparent connection, use the transparent
disconnect sequence you set using SET P. If the transparent connection
could not be established, the SEL-2032 responds with 15h (ASCII
NACK).
READ = "RD\Pa/@\Aa/" READACK = "RP\Dh/" READNACK = ""
To read data from the
SEL-2032 database, use the message format you defined with the
READ
command. To read from Port 7's database at address 1001h
with these settings, send the command
RD07@1001 <Enter>
. The
SEL-2032 will respond with the data if the read is successful (e.g.,
RP0013). If the read cannot be performed, the SEL-2032 will not
respond, because there is no response defined for a failed read
(READNACK) in these settings.
WRITE = "WR\Pa/@\Aa/=\Dh/" WRITEACK = "OK" WRITENACK = "FAIL"
To write data to
the SEL-2032 database, use the message format you have defined with
the
WRITE
command. To write 0036h to Port 11's database at
address D007h with these settings, send the message
WR0B@D007=0036 <Enter>
to the SEL-2032. The SEL-2032
responds “OK” if successful, or “FAIL” if the write could not be
performed.
This example uses ASCII commands, but these commands could also have
been built as binary commands.
SET U Settings
The
SET U
command prompts you for user-defined strings and the command
you want to use to trigger a response on Master, SEL IED, and other IED
ports.
SET U
is not applicable to printer ports. You can also use the
SET U
command to disable the SEL-2032 command set on Master ports.
includes detailed information about the
SET U
settings.
Содержание SEL-2032
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...