Appendix B: Installer Settings Screen - Descriptions
Below are definitions of the options in each screen.
Installer Settings Menu
Setting
Description
Display Lock
Locks the buttons on the thermostat. Refer to the
section for more information.
Service Mode
Service Mode
is used to test an HVAC system. Once in the
Service Mode
menu, the option
Test
Mode
is available and can be set to either
Y
(Yes) or
N
(No). See
Y (Yes)
-
Test Mode
is enabled. When enabled, all delays are reduced to 10 seconds for quicker
system testing. When test mode is enabled, all system delays are shortened. On systems utilizing a
heat pump, do not operate the system compressor in
Test Mode
. Disconnect the
Y1
and
Y2
outputs
if applying
Test Mode
on a live system.
N (No)
-
Test Mode
is disabled. Normal system delays.
Network Settings
Network Addr
- Network Address should be set to
1
. This is the address entered into Blueprint for all
thermostats added to the Savant Control system.
Network Settings
Autosend
- Not supported within a Savant configuration/installation.
Relay Setup
Sets the mode for the auxiliary relays A1 and A2. Refer to the
section for more
information.
SST-W100 Wireless Thermostat Deployment Guide
Copyright © 2016 Savant Systems, LLC
009-0802-08 | 160225