Humidity Settings (Installer Settings Submenu)
Setting
Description
RH Display
The Humidity is displayed on the top right section of the LCD display. To remove the humidity from
being displayed, set the
RH Display
to
O
ff
RH Setpoint
The Relative Humidity setpoint is configured here. The
RH Setpoint
determines when to switch on
auxiliary equipment such as humidifiers and dehumidifiers. The
RH Setpoint
is also used in the
to determine whether to extend a call for cooling.
RH SP Away
Not supported in the
Savant Control
system. All scheduling is achieved through the either the Savant
or TrueControl App.
RH Temp Delta
Used in the HCL logic. Refer to the
RH SP Delta
Used in the HCL logic. Refer to the
RH ON Time
Used in the HCL logic. Refer to the
RH OFF Time
Used in the HCL logic. Refer to the
RH ON Delta
Used in the HCL logic. Refer to the
RH OFF Delta
Used in the HCL logic. Refer to the
System Settings (Installer Settings Submenu)
Setting
Description
Mechanical
Settings
The
HVAC Type
and
Fan Type
is set in the
Mechanical Settings
menu.
Sched Enable
Not supported in the
Savant Control
system. All scheduling functions are achieved through the either
the Savant or TrueControl App. Leave as the default which is
No
.
Away Enable
Not supported in the
Savant Control
system. All scheduling functions are achieved through the either
the Savant or TrueControl App. Leave as the default which is
No
.
Recovery Enable
Not supported in the
Savant Control
system. All scheduling functions are achieved through the either
the Savant or TrueControl App. Leave as the default which is
No
.
H/C Delta
Sets the bu
ff
er zone between the Heat and Cool setpoints. The default is set to 3°.
Fan Purge
Keeps the fan running after either a heating or cooling cycle has ended. Using the
+/-
buttons, the
duration of the purge can be set between 30 and 120 seconds with the default set to 0 seconds (O
ff
).
H Delta Stg1 ON
Configures the number of degrees below the heating setpoint before stage 1 heating is engaged.
Range = 1°F to 6°F (Default = 1°F)
H Delta Stg1 OFF
Applicable after heat stage 1 has been running.
H Delta Stg1
OFF configures the temperature that
heat stage 1 will shut o
ff
. Range = 0°F to 6°F (Default = 0°F)
H Delta Stg2 ON
Configures the number of degrees below the heating setpoint before stage 2 heating is engaged.
Range = 2°F to 7°F (Default = 2°F)
H Delta Stg2 OFF
Applicable after heat stage 2 has been running.
H Delta Stg2
OFF configures the temperature that
heat stage 2 will shut o
ff
. Range = 0°F to 7°F (Default = 0°F)
H Delta Stg3 ON
Configures the number of degrees below the Heating Setpoint before stage 3 heating is engaged.
Range = 3°F to 8°F (Default = 3°F)
H Delta Stg3 OFF
Applicable after heat stage 3 is engaged and running.
H Delta Stg3
OFF configures the temperature
that heat stage 3 will shut o
ff
. Range = 0°F to 8°F (Default = 0°F)
C Delta Stg1 ON
Configures the number of degrees above the Cooling Setpoint before stage 1 cooling is engaged.
Range = 1°F to 7°F (Default = 1°F)
C Delta Stg1 OFF
Applicable after cool stage 1 is engaged and running.
C Delta Stg1
OFF configures the temperature
that cool stage 1 will shut o
ff
. Range = -2°F to 8°F (Default = 0°F)
C Delta Stg2 ON
Configures the number of degrees above the Cooling Setpoint before stage 2 cooling is engaged.
Range = 2°F to 8°F(Default = 2°F)
C Delta Stg2 OFF
Applicable after cool stage 2 is engaged and running.
C Delta Stg2
OFF configures the temperature
that cool stage 2 will shut o
ff
. Range = -2°F to 8°F (Default = 0°F)
Min Run Time
Sets the minimum amount of time a stage must remain on, once it has been turned on. The
Min Run
Time
is configurable from 1 min to 9 min using the
+/-
buttons. (Default = 3 minutes)
SST-W100 Wireless Thermostat Deployment Guide
Copyright © 2016 Savant Systems, LLC
009-0802-08 | 160225
46 of 50