Functions of the heating circuit
30
BA_EQJW126F001_EN001
STOP
on the display indicates that there has been a deviation of flow
temperature of more than 5 °C for longer than 30 minutes. The function is
canceled by the controller in such cases. While
STOP
appears on the display, the
controller keeps the flow tempera- ture constant at 25 °C.
A power failure while the drying function is active or when
STOP
appears on the
display automatically leads to the drying function restarting from the beginning.
NOTICE
The function block parameter can only be accessed when the function has
started by de- activating the function block and activating it again.
Functions
WE
Configuration
Underfloor heating
Drying of jointless floors
0
25 °C
5.0 °C
45.0 °C
4
0.0 °C
SToP
CO1 -> F05 - 1
Start temperature / 20 to 60 °C
Temperature rise per day / 0.0 to 10.0 °C
Maximum temperature / 25.0 to 60.0 °C
Maintaining time for max. temperature / 0 to 10
days
Temperature reduction per day / 0.0 to 10.0 °C
STArT,
STArT,
STArT
5.4
Deactivation depending on outdoor temperature
5.4.1
OT deactivation value in rated operation
If the outdoor temperature exceeds the limit
OT deactivation value in rated
operation
, the affected heating circuit is put out of service immediately. The valve is
closed and the pump is switched off after t = 2 x valve transit time. When the
outdoor temperature falls below this value (less 0.5 °C hysteresis), heating operation
is restarted immediately.
With the default settings, this means that, during the warm season, the system is
switched off at an outdoor temperature of 22 °C.
Parameter
WE
Parameter level /
Range
of
values
OT deactivation
value in rated
operation
22.0 °C
PA1
/ 0.0 to 50.0 °C
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......