System-wide functions
6
System-wide functions
6.1
Automatic summer time/winter time changeover
The clock is automatically adjusted on the last Sunday in March at 2.00h and on
the last Sunday in October at 3.00h.
Function
WE
Configuration
Summer
time/winter
changeover
time
1
CO5 -> F08 -
1
6.2
Frost protection
Frost protection measures are taken when the outdoor temperature falls below the
Frost protection limit.
The switching differential to cancel the frost protection
measures is al- ways 1 °C.
Frost protection program I (restricted frost protection): frost protection
measures are taken only when all heating circuits in the system are in stand-by
mode.
Frost protection program II: the heating circuit circulation pumps are
always swit- ched on automatically. The flow temperature set points of all heating
circuits current-
ly in stand-by mode are set to +10 °C.
Functions
WE
Configuration
Frost protection
program
I
CO5 -> F09 - 0
3.0 °C
Frost protection limit / –15.0 to 3.0 °C
Frost protection
program
II
CO5 -> F09 - 1
3.0 °C
Frost protection limit / –15.0 to 3.0 °C
NOTICE
Frost protection operation of a pump is only active when the frost protection
icon
ap- pears on the display.
In the stand-by mode ) fixed set point control without outdoor temperature
sensor does not include frost protection.
6.3
Forced operation of the pumps
When the heating circuit pump has not been activated for 24 hours, forced
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......