Start-up
BA_EQJW126F001_EN001
21
2.3
Calibrating sensors
The controller is designed for the connection of Pt 1000 sensors.
The resistance values of the Pt 1000 sensors can be found on page 75.
If the temperature values displayed at the controller differ from the actual
temperatures, the measured values of all connected sensors can be readjusted.
To calibrate a sensor, the currently displayed sensor value must be changed such
that it matches the tempera- ture (reference temperature) measured directly at
the point of measurement.
Sensor calibration is to be activated in CO5 via function block
F20. An incorrect sensor calibration can be deleted by setting
F20 - 0.
Proceed as follows:
1.
Turn the rotary switch to (configuration and parameter
level). Display:
0 0 0 0
2.
Set valid key number [
].
3.
Confirm valid key number
]. Display:
PA_
4.
Select CO5 configuration level [
].
5.
Open CO5 configuration level ].
6.
Select function block F20 [
].
7.
Activate editing mode for function block F20 ].
8.
Select appropriate sensor icon [
]:
Room sensor RF, heating circuits
Outdoor sensor AF
Flow sensor VF, heating circuits
Return flow sensor RüF
9.
Display measured value
]. “°C” blinks.
10.
Correct measured value [
].
Read the actual temperature directly from the thermometer at the point of
mea- surement and enter this value as the reference temperature.
11.
Confirm corrected measured value ].
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......