BA_EQJW126F001_EN001
41
Electrical connection
or
Parameter
WE
Parameter level /
Range
of
values
Return flow temp.
points
1 to 4
65.0 °C
PA1
/ 5.0 to 90.0 °C
NOTICE
To ensure that the preset return flow temperature limit can be met, make sure that
–
the heating characteristic is not adjusted to ascend too steeply,
–
the speed of the circulation pumps is not set too high,
–
the heating systems have been calibrated.
6.5
Condensate accumulation control
Activate the
Limit deviation for OPEN signal
function to start up condensate
accumu- lation plants, in particular to avoid problematic excess temperatures.
The controller re- sponse to set point deviations which cause the primary valve to
open is attenuated. The controller response to set point deviations which cause
the control valve to close re- mains unaffected.
Note:
The condensate accumulation control function can only be activated
when the control circuit concerned is controlled using a PI algorithm (three-step
control).
Functions
WE
Configuration
Control mode
1
CO1, 2, 4 -> F12 - 1
Limit
deviation
for
OPEN
signal
0
2.0 °C
CO1, 2, 4 -> F13 - 1
Max. deviation / 2.0 to 10.0 °C
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......