Installation
8.5
Memory module
The use of a memory module (0440210010) is particularly useful to transfer all data
from one EQJW126 Controller to several other EQJW126 Controllers.
The memory module is plugged into the RJ-45 jack at the side. Once the module
has been connected, “73 SP“ is displayed. If the memory module already contains
data from a different EQJW126 Controller, turn the rotary pushbutton until “SP 73"
is displayed.
Pressing the rotary pushbutton to confirm “73 SP“ causes the controller
settings to be transferred to the memory module.
Pressing the rotary pushbutton to confirm “SP 73“ causes the saved
controller set- tings to be transferred from the memory module to the
controller.
During the data transfer, the bars on the display indicate the progress. When the
trans- fer was successful, “I.O.“ is displayed. After that, the connection between
controller and memory module can be terminated.
8.6
Data logging
A data logging module (0440210009) saves the following controller data every two
min utes:
Temperatures measured by the sensors
Control signals [%]
Switching states of the pump outputs
Error status register and its archive data
Access to the controller settings
The data logging module is connected to the RJ-45 jack at the side of the controller.
The controller starts to write over the oldest data as soon the memory of the data
log- ging module is full after approximately eight days. The current memory
capacity of the data logging module can be read in the extended information
level under
Info 2
as the second in the sequence (range of values: 0 to 6035).
Directly after inserting the data logging module, data can be first read after the
first scanning cycle has been performed.
The data log viewer software allows the data to be viewed in graph format. The
USB converter 3 (0440210007) is re quired to connect the data logging mod ule
to a com puter. The data log viewer software is supplied with the USB converter
3.
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......