Functions of the heating circuit
BA_EQJW126F001_EN001
37
crease in flow temperature set point when a sudden deviation in room
temperature arises. A
Gain K
P
setting of 10.0 is recommended.
Functions
WE
Configuration
Room sensors RF
0
CO1 -> F01 - 1
Outdoor sensors AF
1
CO1 -> F02 - 0
Flash adaptation
0
CO1 -> F09 - 1
20 min
Cycle time / 1 to 100 min
0.0
KP (gain) / 0.0 to 25.0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
Parameters
WE
Parameter level /
Range
of
values
Day set point for flow
Night set point for flow
50.0 °C
30.0 °C
PA1
PA1
/ 5.0 to 130.0 °C
/ 5.0 to 130.0 °C
5.8
Adaptation
The controller is capable of automatically adapting the heating characteristic to
the building characteristics, provided a gradient characteristic has been set
(CO1
-> F11 - 0). The reference room, where the room sensor is located, represents the
en- tire building and is monitored to ensure that the room set point (
Day set point)
is main- tained. When the mean measured room temperature in rated operation
deviates from the adjusted set point, the heating characteristic is modified
accordingly for the follow- ing time-of-use. The corrected value is displayed in PA1
parameter levels under
Gradi- ent, flow
.
Functions
WE
Configuration
Room sensors RF
0
CO1 -> F01 - 1
Outdoor sensors AF
1
CO1 -> F02 - 1
Adaptation
0
CO1 -> F08 - 1
Four-point characteristic
0
CO1 -> F11 - 0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......