Functions of the heating circuit
BA_EQJW126F001_EN001
39
ranges of the heating characteristic gradient and the maximum flow temperature
in PA1 parameter level:
Value range of the gradient: 0.2 to 1.0
Value range of the maximum flow temperature: 5 to 50 °C
In addition, it is possible to activate the
Drying of jointless floors
function. In
connec- tion with this, the function block parameters are listed which appear after
activating this function block. They determine the drying process: the first
heating up phase starts at the entered
Start temperature
, which has a flow
temperature of 25 °C in its default set- ting. In the course of 24 hours, this
temperature is raised by the value entered in
Tem- perature rise
, i.e. the default
setting causes the flow temperature set point to rise to 30
°C. If the
Maximum temperature
is reached, it is kept constant for the number of
days entered in
Maintaining time for maximum temperature
. The
Temperature
reduction
de- termines the temperature reduction downwards. If the
Temperature
reduction
is set to 0, the temperature maintaining phase moves directly to
automatic mode. The drying of jointless floor runs to comply with DIN EN 1264 Part
4 when
Start temperature
is set to 25 °C and
Temperature rise per day
to 0.0 °C. As
a result, the function starts with a flow temperature of 25 °C regulated to be kept
constant for three days. Following this, the temperature is increased to the
maximum adjusted temperature. The further process continues as described.
The drying function is activated by changing the setting
STOP
to
START
temperature build-up phase (
STArT
on the display). The restarting stages
START
temperature main- taining phase
(
STArT
on the display) and
START temperature
reduction phase
(
STArT
on the display) can be selected to continue an
interrupted drying process. The course of the drying process can be monitored in
the information level over the icon of flow tem- perature display ( ) of the
associated heating circuit:
Temperature build-up phase
Temperature maintaining phase
Temperature reduction phase
The drying process has been successfully completed when the additional icon in
the flow temperature display goes out after the last phase.
r
r
r
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......