Functions of the heating circuit
38
BA_EQJW126F001_EN001
Note:
If the
Flash adaptation
function is already configured with a small cycle time,
the
Adaptation
function should not be configured as well.
5.9
Cooling control
Cooling control with outdoor sensor
When the cooling control function is activated in a control circuit, the four-point
charac- teristic of the corresponding control circuit is automatically activated
and the operating direction of the control output is reversed. In PA1 the four points
for the course of the set point based on the outdoor temperatures can be
adjusted separately for day and night mode. The
Base point for return flow
temperature
that can be adjusted with an active re- turn flow sensor determines
the point at which a minimum limitation of the return flow temperature starts: If
the measured return flow temperature falls below this value, the flow
temperature set point is raised. The four return flow temperature values in the
four-point characteristic function have no effect.
Functions
WE
Configuration
Cooling control
Four-point characteristic
0
0
CO1 -> F04 - 1
CO1 -> F11 - 1
Parameters
WE
Parameter level /
Range
of
values
Outdoor
Point 1
–15 °C
PA1 / –40 to 50 °C
temperature
Point 2
–5 °C
Point 3
5 °C
Point 4
15 °C
Flow temperature Point 1
70 °C
PA1 / 5 to 130 °C
Point 2
55 °C
Point 3
40 °C
Point 4
25 °C
Reduced flow
Point 1
60 °C
PA1 / 5 to 130 °C
temperature
Point 2
40 °C
Point 3
20 °C
Point 4
20 °C
Base point of return flow
65 °C
PA1 / 5 to 90 °C
temperature
Note:
The
limiting factors of the
Return flow sensor RüF (CO1 -> F03) functions ap-
ply during cooling control as well.
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......