Functions of the heating circuit
BA_EQJW126F001_EN001
35
5.7
Flash adaptation
To ensure that the controller reacts immediately to room temperature deviations
during rated or reduced operation, the function block setting CO1, 2 -> F09 - 1
needs to be made.
The heating is then always switched off as soon as the room temperature exceeds
the
Day set point
or
Night set point
by 2 °C.
Heating first starts again when the room has cooled off and the room temperature
is 1
°C above the
Set point
. The flow temperature set point is corrected if the
Cycle
time
and
Gain K
P
are set to a value other than 0. The
Cycle time
determines the
intervals at which the flow temperature set point is corrected by 1 °C. A
Gain K
P
set
to a value other than 0 causes a direct increase/decrease in flow temperature set
point when a sudden devia- tion in room temperature arises. A
Gain K
p
setting of
10.0 is recommended.
Note:
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated after the cooling load has been
eliminated!
Functions
WE
Configuration
Room sensors RF
0
CO1 -> F01 - 1
Flash adaptation
0
CO1 -> F09 - 1
20 min
Cycle time / 0 to 100 min
0.0
KP (gain) / 0.0 to 25.0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
5.7.1 Flash adaptation without outdoor sensor
The flow temperature control starts with
Day set point for flow
in rated operation or
with
Night set point for flow
in reduced operation as no set points calculated using
character- istics exist without an outdoor sensor. The
Cycle time
determines the
intervals at which the flow temperature set point is corrected by 1 °C. The heating
is then always switched off as soon as the room temperature exceeds the
Day set
point
or
Night set point
by 2 °C. Heating first starts again when the room has
cooled off and the room temperature is 1
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......