44
BA_EQJW126F001_EN001
Electrical connection
6.10
Locking the rotary switch
When this function has been activated, the controller remains in automatic
mode re- gardless of the rotary switch position. The rotary switch can no longer be
used to adjust the controller settings. It is still posssible to enter the key number.
Function
WE
Configuration
Locking the rotary switch
0
CO5 -> F22 -
1
6.11
Setting a customized key number
To avoid the unauthorized modification of functions and parameters of the
controller, the default key number can be replaced with an individual key
number.
Choose your custom key number between 0100 and 1900.
Proceed as follows:
1.
Turn the rotary switch to (configuration and parameter
level). Display:
0 0 0 0
2.
Set key number 1995 [
].
3.
Confirm key number ].
4.
Enter valid key number [
].
5.
Confirm key number ].
Key number blinks.
6.
Adjust desired custom key number [
].
7.
Confirm custom key number ].
This new key number is now
valid.
8.
Return rotary switch to the standard switch position (information level).
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......