Appendix
BA_EQJW126F001_EN001
63
12
Appendix
12.1 Function block lists
CO1: Rk1· Heating circuit 1
F
Function
WE
Anl
Comment
Function block parameters / Range of values (default)
01
Room sensor RF
0
Not in
Anl 1.5,
1.6, 3.x
CO1 -> F01 - 1: Temperature display and input FG1 for
Type 5257-5 Room Panel active
02
Outdoor
sensor AF
0
1.5, 1.6
CO1 -> F02 - 1: Weather-compensated control active
1
Not in
Anl 1.5,
1.6
03
Return flow
sensor RüF
0
1.2
CO1 -> F03 - 1: Sensor and limiting function active
Function block parameter:
KP (limiting factor) / 0.1 to 10.0 (1.0)
1
Not in
Anl 1.2
04
Cooling control
0
All*
CO1 -> F04 - 1: Cooling control, only with CO1 ->
F11 - 1
The cooling control causes the reversal of the
operating direction and a minimum limitation of the
return flow
temperature in Rk1.
05
Underfloor
heating
Drying of jointless
floors
0
Not in
Anl 1.5,
1.6, 3.x
CO1 -> F05 - 1: Limitation of the adjustment ranges
Function block parameters:
Start temperature / 20 to 60 °C (25 °C)
Temperature rise per day / 0.0 to 10.0 °C (5.0
°C) Maximum temperature / 25.0 to 60.0 °C
(45.0 °C)
Maintaining time of max. temp. / 0 to 10 days (4
days) Temperature reduction per day / 0.0 to 10.0 °C
(0.0 °C)
SToP,
STArT,
STArT,
STArT
07
Optimization
0
Not in
Anl 1.5,
1.6, 3.x
CO1 -> F07 - 1: Only with• CO1 -> F01 - 1
•
CO1 -> F02 - 1
08
Adaptation
0
Not in
Anl 1.5,
1.6, 3.x
CO1 -> F08 - 1: Only with• CO1 -> F01 - 1
•
CO1 -> F02 - 1
•
CO1 -> F11 - 0
09
Flash adaptation
0
Not in
Anl 1.5,
1.6, 3.x
CO1 -> F09 - 1 Only with CO1 -> F01 - 1
Function block parameters:
Cycle time / 0 or 1 to 100 min (20 min)
KP (gain) / 0.0 to 25.0 (0.0)
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......