Functions of the heating circuit
BA_EQJW126F001_EN001
33
3
°
C
/
Function
WE
Configuration
Summer mode
0
CO5 -> F04 - 1
01.06
Start summer mode/ 01.01 (1 Jan) to 31.12 (31
2
Dec)
30.09
No. of days until activation / 1 to 3
1
Stop summer mode / 01.01 to 31.12
18.0 °C
No. of days until deactivation / 1 to 3
OT limit value summer mode / 0 to 30 °C
Note:
Summer mode only becomes effective when the controller is in automatic mode
).
5.5
Delayed outdoor temperature adaptation
The calculated outdoor temperature is used to determine the flow temperature
set point. The heat response is delayed when the outdoor temperature either
decreases, in- creases or increases and decreases. If the outdoor temperature
varies by, for example, 12 °C within a very short period of time, the calculated
outdoor temperature is adapted to the actual outdoor temperature in small steps.
Assuming a
Delay
of 3 °C/h, the adap- tation would take
t
=
12
°
C
=
4
h
.
Note:
The delayed outdoor temperature adaptation helps avoid unnecessary
overloads of cen- tral heating stations in combination with either overheated
buildings occurring, for exam- ple, due to warm winds, or temporarily insufficient
heating due to the outdoor sensor be- ing exposed to direct sunshine.
In the information level, the outdoor temperature blinks on the display while
delayed out- door temperature adaptation is active. The calculated outdoor
temperature is displayed.
Functions
WE
Configuration
Delayed OT adaptation when OT decreases
0 CO5 -> F05 - 1
Delayed OT adaptation when OT increases 0
CO5 -> F06 - 1
3.0 °C Delay per hour / 1.0 to 6.0 °C
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......