Installation
BA_EQJW126F001_EN001
57
9
Installation
The controller is available either with a standard back panel or a high back panel.
Dimensions in mm (W x H x D)
Controller with standard back panel : 144 x 98 x 54
The controller consists of the housing with the electronics and the back panel
with the terminals. It is suitable for panel, wall and top hat rail mounting (Fig. 6).
Panel mounting
1.
Remove both screws (1).
2.
Pull apart the controller housing and the back panel.
3.
Make a cut-out of 138 x 92 mm (W x H) in the control panel.
4.
Insert the controller housing through the panel cut-out.
5.
Tighten the two screws (2) to clamp the controller housing against the control
panel.
6.
Connect the electrical wiring at the back of the housing as described in section
7.
Fit the controller housing.
8.
Fasten both screws (1).
Wall mounting
1.
Remove both screws (1).
2.
Pull apart the controller housing and the back panel.
3.
If necessary, drill holes with the specified dimensions in the appropriate
places. Fasten the back panel with four screws.
4.
Connect the electrical wiring at the back of the housing as described in section
5.
Remount the controller housing.
6.
Fasten both screws (1).
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......