Appendix
64
BA_EQJW126F001_EN001
F
Function
WE
Anl
Comment
Function block parameters / Range of values (default)
11
Four-point
characteristic
0
Not in
Anl 1.5,
1.6
CO1 -> F11 - 1: Four-point characteristic, only with
CO1 -> F08 - 0
CO1 -> F11 - 0: Gradient characteristic
12
Control mode
1
All*
CO1 -> F12 - 1: three-step control
Function block parameters:
KP (proportional gain) / 0.1 to 50.0 (2.0)
Tn (reset time) / 1 to 999 s (120 s)
TV (derivative-action time) / 0 to 999 s (0 s)
TY (valve transit time) / 5, 10, 15, …, 240 s (45 s)
CO1 -> F12 - 0: On/off control
Function block parameters:
Hysteresis / 1.0 to 30.0 °C (5.0 °C)
Min. ON time / 0 to 10 min (2 min)
Min. OFF time / 0 to 10 min (2 min)
13
Limitation
of
deviation
for OPEN
signal
0
All*
CO1 -> F13 - 1 only with CO1 -> F12 - 1
Function block parameter:
Max. deviation / 2.0 to 10.0 °C (2.0 °C)
14
Release Rk1
at BE1
0
All*
With CO1 -> F14 - 1, FG1 has no function;
Options
bE= 1, bE=0 (bE=1)
15
Processing an
external
demand in Rk1
0
All*
How the external demand is processed in Rk1
depends on CO1 -> F16, CO1 -> F17 and CO7 -> F15.
16
Processing an
external
demand, 0 to 10
V
Input term. 11/12
0
All*
CO1 -> F16 - 1: Only with• CO1 -> F15 - 1
•
CO1 -> F17 - 0
Function block parameters:
Lower transmission range: 0.0 to 130.0 °C (0.0 °C)
Upper transmission range: 0.0 to 130.0 °C (120.0 °C)
The standard signal output (terminals 11/12) is not
available anymore as a control output.
17
Processing an
external
demand, binary
Input term. 03/12
0
Not in
Anl with
SF2/RF2
CO1 -> F17 - 1: Only with
• CO1 -> F15 - 1
•
CO1 -> F16 - 0
Options
bE= 1, bE=0 (bE=1)
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......