Operational faults
7.2
Sensor failure
According to the error list, sensor failures are indicated by displaying “Err 1“ error
message in the error level. For detailed information, exit error level and view the
differ- ent temperature values in the information level: each sensor icon
displayed together with 3 horizontal lines instead of the measured value indicates
a defective sensor. The following list explains how the controller responds to the
failure of the different sensors.
Outdoor sensor AF
: When the outdoor sensor fails, the controller uses a flow
tem- perature set point of 50 °C or the
Max. flow temperature
when the
Max.
flow tempe- rature
(adjusted at PA1) is lower than 50 °C.
Flow sensor in heating circuit
: When the flow sensors in the heating circuits
are defective, the associated valve moves to 30 % travel.
Return flow sensors RüF
: When the return flow sensor fails, the controller continu-
es operation without return flow temperature limitation.
Room sensors RF
: When the room sensor fails, the controller uses the
settings foroperation without room sensor. The controller, for example, switches
from optimi-
zing mode to reduced operation; adaptation mode is canceled. The last
determined heating characteristic remains unchanged.
7.3
Temperature monitoring
When a system deviation greater than 10 °C persists in a control circuit for 30
minutes, an “Err 6“ error message (temperature monitoring alarm) is generated.
Function
WE
Configuration
Temperatur
e
monitoring
0
CO5 -> F19 -
1
7.4
Error status register
The error status register is used to indicate controller or system errors. In modem
opera- tion mode when the controller dials the building control system (GLT) both
when an er- ror is detected and when it has been corrected, each change in
the status of the error status register causes the controller to dial the control
system. You can define which er- ror messages are to influence the error status
register after entering the key number 0025. The default setting of 465 results in just
the error messages highlighted in the ta- ble (bold) causing a change in state of
the error status register.
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......