Octet
Bit Explanation
Note
13
4…7 Reserved in Profile 3.01
14
0…6 Reserved in Profile 3.01
7 EXTENSION_AVAILABLE (further diagnostic information available)
15
3)
0 Device not initialized
1 Solenoid valve active
2 Total valve travel limit exceeded (see Code 24)
3 Control loop (see Code 57)
4 Zero point (see Code 58)
5 Autocorrection (see Code 59)
6 Fatal error (see Code 60)
7 Extended diagnostics (only available with EXPERT
+
)
2
16
3)
0 x > range (see Code 50)
1 Delta x < range (see Code 51)
2 Attachment (see Code 52)
3 Initialization time exceeded (see Code 53)
4 Initialization/solenoid valve (see Code 54)
5 Travel time too short (see Code 55)
6 Pin position (see Code 56)
16
3)
7 Test or calibration running
17
3)
0 x signal (see Code 62)
1 i/p converter (see Code 64)
2 Hardware (see Code 65)
3 Control parameter (see Code 68)
4 Potentiometer parameter (see Code 69)
5 Calibration parameter (see Code 70)
6 Internal device error 1 (see Code 73)
7 General parameter (see Code 71)
32
KH 8384-4 EN
Standard
diagnostics with PROFIBUS-DP protocol
Содержание 3730-4
Страница 4: ...4 KH 8384 4 EN...
Страница 99: ...KH 8384 4 EN 99...