8.1.1 Physical Block, Slot 0
· Manufacturer-specific parameters
ACTIVE_IDENT_NUMBER (137)
Storage class: – · Read capability (r)
GSD file used to run the positioner
If the positioner is in the compatibility mode, it can run using the following GSD files:
• 3785:
3785 Profile 2
• 071D:
3785 Profile 3
• 0688:
3730-4 Profile 3.01
CONDENSED_STATUS (133)
Storage class: – · Read capability (r)
Condensed state according to NAMUR
CONFIG_BINARY_INPUT_2 (59)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Configuration of the second binary input
• 0 · Floating contact – DI2 · The input is analyzed with the second DI Function Block.
• 1 · Actively open – Diagnosis leakage sensor – DI2 · A leakage sensor is operated at the input as ac-
tively open. This information is reported by the extended diagnostics as “External leakage may exist”
and can be analyzed with Function Block DI2.
• 2 · Actively closed – Diagnosis leakage sensor – DI2 · A leakage sensor is operated at the input as
actively closed. This information is reported by the extended diagnostics as “External leakage may
exist” and can be analyzed with Function Block DI2.
• 3 · Solenoid valve – CB_FAIL_SAFE/DI2 · The internal solenoid valve is used and the information (so-
lenoid valve wired same as 1) is analyzed with Function Block DI2. This information is also trans-
mitted cyclically with CHECKBACK (CB_FAIL_SAFE). The input is not switched.
• 4 · Actively open – Diagnosis leakage sensor/CB_ADD_INPUT/Solenoid valve – DI2 · A leakage
sensor is operated at the input as actively open. This information is also transmitted cyclically with
CHECKBACK (CB_ADD_INPUT). Additionally, the state of the internal solenoid valve is switched to
Function Block DI2.
• 5 · Actively closed – Diagnosis leakage sensor/CB_ADD_INPUT/Solenoid valve – DI2 · A leakage
sensor is operated at the input as actively closed. This information is also transmitted cyclically with
CHECKBACK (CB_ADD_INPUT). Additionally, the state of the internal solenoid valve is switched to
Function Block DI2.
• 6 · Actively open – Diagnosis leakage sensor/CB_ADD_INPUT/Solenoid valve – DI2 · A leakage
sensor is operated at the input as actively open. This information can be analyzed with Function
Block DI2. Additionally, the state of the internal solenoid valve is also transmitted cyclically with
CHECKBACK (CB_ADD_INPUT).
KH 8384-4 EN
47
Physical Block, Slot 0
· Manufacturer-specific parameters
Содержание 3730-4
Страница 4: ...4 KH 8384 4 EN...
Страница 99: ...KH 8384 4 EN 99...