![Samson 3730-4 Скачать руководство пользователя страница 65](http://html2.mh-extra.com/html/samson/3730-4/3730-4_configuration-manual_3871966065.webp)
IN_CHANNEL (37)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Assignment between the Transducer Block and the Function Block
• 0 · Not active
• 0x013A · Active (FEEDBACK_VALUE is written to READBACK)
INCREASE_CLOSE (52)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Determines the direction of action, i.e. how the reference variable is assigned to the controlled variable
• Increasing/increasing
• Increasing/decreasing
MODE_BLK (22)
Storage class: – · Read capability (r)
Current mode
OUT (53)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Output value
This output value is calculated by the Function Block from the SETPOINT for the Transducer Block in
[mm], [degrees] or [%]
OUT_CHANNEL (38)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Assignment between the Transducer Block and the Function Block
• 0 · Not active
• 0x0139 · Active (OUT is written to POSITIONING_VALUE)
OUT_SCALE (54)
Storage class: S · Read/write capability (r/w) · Supported modes: O
Travel range or angle of rotation
Upper and lower values of the actual working range in [mm] or [degrees]. A non-linear characteristic is
adapted to the reduced travel.
Maximum value for upper value = Rated travel
KH 8384-4 EN
65
AO Function Block, Slot 1
· Profile-specific parameters