Byte
Bit
According to PA V3.01
Description
2
0
DIA_MAINTENANCE_ALARM
Device error exists
2
1
DIA_MAINTENANCE_DEMANDED Maintenance demanded
2
2
DIA_FUNCTION_CHECK
Device performing a function check or it is in
simulation or in MODE_LO
2
3
DIA_INV_PRO_COND
The current process conditions do not allow a
valid calculation of values
2
4…7
–
3
0…7
–
4
0…6
–
4
7
EXTENSION_AVAILABLE
Further diagnostic data available
see DIAGNOSIS_EXT/
DIAGNOSIS_EXTENSION_2
DIAGNOSIS_EXT (30)
Storage class: – · Read capability (r)
Byte
Bit
Description
0
0
Device not initialized
0
1
Solenoid valve active
0
2
LV total valve travel
(Code 24)
0
3
Control loop error
(Code 57)
0
4
Zero point error
(Code 58)
0
5
Autocorrection
(Code 59)
0
6
Fatal error
(Code 60)
0
7
Extended diagnostics available · Only with EXPERTplus
1
0
x > range
(Code 50)
1
1
Delta x < range
(Code 51)
1
2
Attachment
(Code 52)
1
3
Initialization time exceeded
(Code 53)
1
4
Initialization solenoid valve
(Code 54)
1
5
Transit time too short
(Code 55)
1
6
Pin position
(Code 56)
1
7
Test or calibration in progress
2
0
x signal
(Code 62)
2
1
i/p converter
(Code 64)
2
2
Hardware error
(Code 65)
2
3
Control parameter error
(Code 68)
2
4
Potentiometer parameter error
(Code 69)
2
5
Calibration
(Code 70)
2
6
No production calibration
2
7
General parameters
(Code 71)