Fault/diagnostic alarm
Default setting acc. to Pro-
file 3.01 Condensed Status
Classified
Diagnosis
Yes
No
Mostly max. opening
0x80 GOOD_NON_SPECIFIC
•
–
Temperature monitoring
Lower limit exceeded
0x80 GOOD_NON_SPECIFIC
•
–
Higher limit exceeded
0x80 GOOD_NON_SPECIFIC
•
–
Reference run
Reference test aborted
0x80 GOOD_NON_SPECIFIC
•
–
ESD
Movement actuator possible –>
Masking redundant
0x80 GOOD_NON_SPECIFIC
•
–
Movement actuator impossible
0x80 GOOD_NON_SPECIFIC
•
–
Solenoid valve error
0x80 GOOD_NON_SPECIFIC
•
–
Function activated
Initialization active
0xBC GOOD_NON_SPECIFIC
•
1)
–
Diagnostic function active
0xBC GOOD_NON_SPECIFIC
•
1)
–
1)
Can be classified either as GOOD_FUNCTION_CHECK or BAD_FUNCTION_CHECK in firmware K 1.10 and
higher. See FEATURE_SELECT parameter on page 54.
5.5
Standard diagnostics with PROFIBUS-DP protocol
Generated alarms are classified and summarized in the PROFIBUS Profile 3.01 and 'Con-
densed status and diagnostic messages' extension.
The diagnostic approach complying with PROFIBUS-DP includes the following types of diag-
nostic transfer:
4
The DP master class 1 reads the diagnosis of the DP slave while the cyclic data exchange
is being set up.
4
In case of an active diagnostic alarm, the slave responds during the data exchange with a
high-prioritized response telegram.
The master requests a diagnosis as a result to continue afterwards with the normal data
exchange.
KH 8384-4 EN
29
Measured value status and valve diagnostics
Содержание 3730-4
Страница 4: ...4 KH 8384 4 EN...
Страница 99: ...KH 8384 4 EN 99...