• 29
Reset 'Travel histogram x - short-term monitoring'
• 30
Reset 'Setpoint deviation histogram e - short-term monitoring'
• 31
Reset 'Cycle counter histogram - short-term monitoring'
• 32
Reset 'Drive signal diagram hysteresis - short-term monitoring'
• 38
Reset 'Drive signal diagram steady-state - measured data'
• 39
Reset 'Drive signal diagram hysteresis - measured data'
• 60
Reset partial stroke test (PST)
• 61
Reset full stroke test (FST)
SELF_CALIB_STATUS_2 (233)
Storage class: – · Read capability (r)
SELF_CALIB_WARNING (167)
Storage class: – · Read capability (r)
Initialization error
SET_FAIL_SAFE_POS (178)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Fail-safe position of the valve
The positioner remains in AUTO mode. The fail-safe position is indicated on the positioner display by a
blinking "S".
• 0 · Not active
• 1 · Set fail-safe position
• 2 · Reset fail-safe position
SETP_CUTOFF_DEC_ON (171)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Activate/deactivate setpoint cutoff decrease (final position w <)
SETP_CUTOFF_INC_ON (170)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Activate/deactivate setpoint cutoff increase (final position w >)
SIGNAL_PRESSURE_ACTION (176)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Position of the slide switch AIR TO OPEN/AIR TO CLOSE (for initialization)
It can only be changed by re-initializing the positioner.
88
KH 8384-4 EN
AO Transducer Block, Slot 1
· Manufacturer-specific parameters