• 7 · Calibration sequence mixed up
• 8 to10 · –
• 11 · Timeout
• 12 · Proportional range restricted too much
• 13 · Rated travel or transmission incorrectly selected
• 14 · Mechanics system stuck (during initialization)
• 15 · Pneumatics system leaks (during initialization)
• 16 · Action interrupted as a production test has not yet been performed successfully
• 17 · Initialization status: Mechanical stops determined
• 18 · Initialization status: Minimum control pulse determined
• 19 · Initialization status: Minimum transit times determined
• 20 · Initialization canceled by activation of the solenoid valve
• 21 to 29 · –
• 30 = Zero point error
• 31 to 253 · –
• 254 = Successful
• 255 = No valid data from the closed-loop control
SERVO_GAIN_1 (115)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
K
P
step (Code 17)
• [7]
SERVO_RATE_1 (116)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
T
V
step (Code 18)
• [2]
SETP_CUTOFF_DEC (118)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Final position w < (Code 14)
If the reference variable falls below the entered value, the valve moves towards the final position which
corresponds to 0 % reference variable.
Electropneumatic actuators are completely filled with air or vented (depending on the fail-safe position).
• [0.0 %]
KH 8384-4 EN
73
AO Transducer Block, Slot 1
· Profile-specific parameters