Fault/diagnostic alarm
Value (hex) Status alarm acc. to
Profile 3.01
Observing end position
Zero point shift monotonously downwards, average value above
reference lines
0x80
GOOD_NON_SPECIFIC
Zero point shift monotonously upwards, average value above
reference lines
0x80
GOOD_NON_SPECIFIC
Zero point alternating, average value above reference lines
0x80
GOOD_NON_SPECIFIC
Zero point shift monotonously downwards, average value below
reference lines
0x80
GOOD_NON_SPECIFIC
Zero point shift monotonously upwards, average value below
reference lines
0x80
GOOD_NON_SPECIFIC
Zero point alternating, average value below reference lines
0x80
GOOD_NON_SPECIFIC
Connection positioner/valve
No optimal travel transmission (TEST)
0x80
GOOD_NON_SPECIFIC
Perhaps loose
0x80
GOOD_NON_SPECIFIC
Perhaps limit. range
0x80
GOOD_NON_SPECIFIC
Perhaps loose (TEST)
0x80
GOOD_NON_SPECIFIC
Range
Mostly near closing position
0x80
GOOD_NON_SPECIFIC
Mostly near max. opening
0x80
GOOD_NON_SPECIFIC
Mostly closing position
0x80
GOOD_NON_SPECIFIC
Mostly max. opening
0x80
GOOD_NON_SPECIFIC
Temperature monitoring
Lower limit exceeded
0x80
GOOD_NON_SPECIFIC
Higher limit exceeded
0x80
GOOD_NON_SPECIFIC
Reference run
Reference test aborted
0x80
GOOD_NON_SPECIFIC
ESD
Movement actuator possible –> Masking redundant
0x80
GOOD_NON_SPECIFIC
Movement actuator impossible
0x80
GOOD_NON_SPECIFIC
Solenoid valve error
0x80
GOOD_NON_SPECIFIC
24
KH 8384-4 EN
Measured value status and valve diagnostics