Fault/diagnostic alarm
Value (hex) Status alarm acc. to
Profile 3.01
Function activated
Initialization active
0x80
GOOD_NON_SPECIFIC
Diagnostic function activated
0x80
GOOD_NON_SPECIFIC
5.4
Status alarms according to Profile 3.01 Condensed Status
Fault/diagnostic alarm
Default setting acc. to Pro-
file 3.01 Condensed Status
Classified
Diagnosis
Yes
No
Operational error
Device not initialized
0x24 BAD_MAINT_ALARM
•
DIA_INIT_ERR
Solenoid valve active
0x80 GOOD_NON_SPECIFIC
•
–
Total valve travel exceeded
0xA4 GOOD_MAINT_REQ
•
DIA_MAINTENANCE
Control loop error
0xA4 GOOD_MAINT_REQ
•
DIA_MAINTENANCE
Zero point error
0xA4 GOOD_MAINT_REQ
•
DIA_ZERO_ERR
Autocorrection
0x80 GOOD_NON_SPECIFIC
•
DIA_MAINTENANCE
DIA_MEM_CHECKSUM
Fatal error
0x24 BAD_MAINT_ALARM
•
DIA_HW_ELECTR
Extended diagnostics available
0x80 GOOD_NON_SPECIFIC
•
DIA_MAINTENANCE
EXTENSION_AVAILABLE
No emergency mode
0xA4 GOOD_MAINT_REQ
•
DIA_MEM_CHECKSUM
Temperature < –40 °C
0x80 GOOD_NON_SPECIFIC
•
–
Temperature > 80 °C
0x80 GOOD_NON_SPECIFIC
•
–
Initialization error
x > range
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Delta x < range
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Incorrect attachment
(mechanics/pneumatics)
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Initialization time exceeded
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Solenoid valve initialization
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Transit time too short
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Pin position
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR