![Samson 3730-4 Скачать руководство пользователя страница 74](http://html2.mh-extra.com/html/samson/3730-4/3730-4_configuration-manual_3871966074.webp)
SETP_CUTOFF_INC (119)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Final position w > (Code 15)
If the reference variable exceeds the entered value, the valve moves towards the final position which
corresponds to 100 % reference variable.
Electropneumatic actuators are completely filled with air or vented (depending on the fail-safe position).
• [125.0 %]
ST_REV (81)
Storage class: – · Read capability (r)
Revision level of static data
STRATEGY (83)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Grouping to allow faster processing of blocks
• [0]
Blocks are grouped by entering the same value in the STRATEGY parameter of each block.
TAG_DESC (82)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Used to enter a user-selected text to identify and assign blocks.
• Max. 32 characters, [no text]
TARGET_MODE (85)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Target mode
• [8] · AUTO (automatic mode)
• 16 · MAN (manual mode)
• 128 · O/S (out of service)
TOT_VALVE_TRAV_LIM (126)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Limit value for the total valve travel (Code 24)
• [1000000.0]
TOTAL_VALVE_TRAVEL (125)
Storage class: – · Read capability (r)
Total valve travel: Totaled double valve travel (Code 23)
74
KH 8384-4 EN
AO Transducer Block, Slot 1
· Profile-specific parameters
Содержание 3730-4
Страница 4: ...4 KH 8384 4 EN...
Страница 99: ...KH 8384 4 EN 99...