background image

30

SALICRU

5.5.3.  Connection of the output, terminals 

(X6 to X9)

.

 

As it is an equipment with protection against class I 

electrical shock, it is essential to install the protec-

tive earth conductor to the terminal identified as 

. Con-

nect this conductor before supplying voltage to the input 

terminals.

 

Connect the output cables to the respective terminals ac-

cording to the configuration of the available equipment, 

considering the illustrations in Fig. 5 to 10 in terms of the 

connection points of the cables.

 

ˆ

Three-phase output connection:

Connect the loads to the U-V-W-N output terminals, 

respecting the rotation of the phases and the neu-

tral 

indicated in the labelling of the equipment and in 

this manual. If the phase rotation is not respected the 

equipment will not work.

Where there are discrepancies between the labelling 

and the instructions in this manual, labelling shall al-

ways prevail.

 

ˆ

Single-phase output connection:

Connect the loads to the U-N output terminals, re-

specting the rotation of the phase and the neutral in-

dicated in the labelling of the equipment and in this 

manual. Failure to observe the phase and neutral rota-

tion will cause serious damage to the equipment.

Where there are discrepancies between the labelling and 

the instructions in this manual, labelling shall always pre-

vail.

For systems in parallel, it will be necessary to repeat the 

connections that go from the panel to each equipment.

 

Frequency converter mode.

 You can use the 

equipment with the frequency converter configura-

tion, activating this function through the control panel 

menus. For connection purposes, the order of connection of 

the phase or phase and neutral cables to the load or loads 

shall be respected.

 

With regard to the protection to be placed at the output 

of the protection panel or manual bypass, we recommend 

the distribution of the output power in at least four lines. 

Each of them will have a circuit breaker switch of adequate 

value. This type of output power distribution will allow that 

in the event of a fault in any of the devices connected to the 

equipment, which provokes a short circuit, does not affect 

more than the line that is broken. The remaining connected 

loads will have continuity assured due to the tripping of 

the protection, only in the line affected by the short circuit.

5.5.4.  Connection of the battery terminals of the 

equipment with those of the battery module.

The battery set can be set to 32, 36, 40 or 44 elements con-

nected in serial, but always in even numbers since it is neces-

sary for the internal architecture of the equipment to have a 

central point or mid tap -N neutral-. At the same time, the back-

up time together with the power required to feed the loads de-

termines the Ah capacity of the batteries.

Batteries connected in serial

N

BAT –

BAT +

N/2

N/2 +1

N–1

N

2

1

+               N

–               

Fig. 27. 

Typical connection of battery set.

 

As it is an equipment with protection against class I 

electrical shock, it is essential to install the protec-

tive earth conductor to the terminal identified as 

. Con-

nect this conductor before supplying voltage to the input 

terminals.

 

The connection between the terminals of the cabinet or 

battery pack and the UPS will always be made through the 

supplied cable bundle, respecting the polarity indicated in 

the labelling of each unit and the colour of the cables or 

their identification at the ends through heat shrink sleeve 

(red for positive ‘+’, blue for common 'N' and black for nega-

tive '-').

It is imperative to respect this rule and not to extend the 

bundle supplied.

 

For extended back-up time in which more than one module 

or battery cabinets are supplied, the connection will always 

be in parallel between them and in turn with the equip-

ment. Respect the rule indicated in the previous point for 

the connection.

 

For the subracks of 6 slots in parallel will not change the 

connection of the batteries with the UPS, since each group 

of batteries connects directly with its UPS.

However, there is also another possibility, a set of batteries 

inside a cabinet or installed on a rack, common for a sub-

rack system with 6 slots in parallel.

 

Danger of electric shock

. If after starting up the 

UPS, it is necessary to disconnect the battery cabinet, 

it must carry out a complete shutdown of the equipment.

Open the battery fuse holder switch 

(F3)

 or the battery dis-

connect switch 

(Q8)

 located in the accumulators cabinet 

and/or the fuse holder switch or disconnect switch 

(Q3)

on the UPS.

Wait at least 5 minutes until the filter capacitors have been 

discharged.

5.5.5.  Earth bonding terminal connection.

 

As it is an equipment with protection against class I 

electrical shock, it is essential to install the protec-

tive earth conductor to the terminal identified as 

. Con-

nect this conductor before supplying voltage to the input 

terminals.

 

Make sure that all loads connected to the UPS are only con-

nected to this ground terminal. Failure to limit the grounding 

of the load or loads and the cabinet or battery cabinets to 

this single point will create loops back to ground that will 

degrade the quality of the power supplied.

Содержание SLC ADAPT X Series

Страница 1: ...SLC serie ADAPT X UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL...

Страница 2: ...HECONNECTIONCABLES 5 4 PROTECTIVEDEVICESANDCROSSSECTIONOFTHE CONNECTIONCABLES 5 4 1 Input bypassandoutput 5 4 2 Batteryinstallationandmaintenance 5 4 2 1 Generalrecommendations 5 4 2 2 Installing the...

Страница 3: ...TDATEANDTIME 6 11 LEVEL1CONTROLPASSWORD 7 MONITORING PANEL WITH LCD TOUCH SCREEN 7 1 INTRODUCTION 7 2 DIAGRAMOFENERGYFLOWTOLEDS 7 2 1 Acousticalarm 7 3 DESCRIPTIONOFTHESCREENSSHOWNONTHELCD TOUCHSCREEN...

Страница 4: ...urate we are not responsible for any errors or omissions that may exist The images included in this document are for illustrative purposes and may not represent exactly the parts of the equipment show...

Страница 5: ...le the customer can perform these adaptations on their own or otherwise we can also manufacture any configuration on demand For those systems shipped from the factory and assembled in a rack cabinet w...

Страница 6: ...r WARNING This is a category C3 UPS This is a product for commer cial and industrial application in the second environ ment Installation restrictions or additional measures may be necessary to avoid d...

Страница 7: ...possible input and output configurations The subracks incorporate a control panel with 7 colour touch screen as an interface between the equipment and the end user which provides different informatio...

Страница 8: ...wer terminals see Fig 6 to 11 Power terminal cover Acoustic alarm EPO pushbutton Led Status Manual bypass block Handle Module No 1 No 2 No 3 No 4 Control and Bypass Led synoptic of module Trim for cab...

Страница 9: ...o 3 No 4 No 5 No 6 Control and Bypass Led synoptic of module Trim for cable passage Swivel castors with brake Cable gland on frame base Synoptic LEDs and control panel keypad SNMP Slot RS232 RS485 Acc...

Страница 10: ...ar customer specifications CO MadeinSpain MarkinginUPSandpackaging forcustoms W Neutral mark equipment BC Common battery set parallel subracks 100A Protection size 213 Three last digits of the type 2...

Страница 11: ...or distribu tors It is not allowed or authorized to change the configuration by the end user since this involves the modification of copper rods between the power terminals by the addition or removal...

Страница 12: ...erminals of the phases of both blocks by means of the copper rods in order to have a single common input When separate power supplies are required it is man datory to remove the copper rods between ph...

Страница 13: ...d in case of overload or fault it will automatically transfer to the static bypass line In order to provide a clean transfer without no break between the inverter output and the bypass line they must...

Страница 14: ...UPS modules have hardware and software that is suit able and compatible with the requirements of parallel sys tems Although all modules installed in a subrack are internally connected in parallel the...

Страница 15: ...se single phase configuration and separate inputs Bat Bat N Bat OUTPUT N BYPASS R INPUT BYPASS N R S T INPUT OUTPUT U Terminal block in 2 slot and 4 slot subrack BATT N BYPASS R N INPUT R S T N OUTPUT...

Страница 16: ...Isolation transformers are optionally available for installations where both sources do not share the same neutral reference or where it is not available 4 3 3 Operating modes The modular system descr...

Страница 17: ...commer cial AC grid DANGER During Manual Bypass Mode the input output and by pass terminals version B are under potential although all modules are off It is recommended in this operating mode Remove t...

Страница 18: ...ustable between 1 6 to 1 75 V cell VRLA 4 3 4 2 Advanced functions Two battery related tests can be performed as long as there are no alarms or warnings on the UPS Battery test Transfer the system to...

Страница 19: ...ched to the impact indicator located on the packaging Unpacking To check the contents it is necessary to remove the packaging Complete the unpacking according to the proce dure of section 5 1 3 Conten...

Страница 20: ...al at tention to the subrack with 6 slots as incorporating castors could fall from the pallet and cause an accident beyond the material damage itself 5 1 4 Transport to the site If the receiving area...

Страница 21: ...flow of the room The stability and ambient temperature of the room where the battery is located is an important factor that determines the capacity to store the energy during the chemical pro cess tha...

Страница 22: ...equipment intended for installation inside a rack cabinet the following actions will be performed according to the model for adaptation Consider that the illustrations in Fig 22 although they belong t...

Страница 23: ...ction of the remaining ones continuing for the one located at the highest point of the subrack f g Fig 22 Previous steps for the installation of the subrack in rack cabinet h i Fig 23 Installation of...

Страница 24: ...s the trim itself is used to pass the dry contact signals see Fig 28 k The mounting of the terminal protection cover of the subrack on its rear side can be removed and omitted since the cabinet will h...

Страница 25: ...a and single line diagrams on the connection of the system to the installation are also available These data are useful for determining the minimum protec tions and cross cable sections to be installe...

Страница 26: ...spillage of the electrolyte Be sure to replace the battery before this happens If a battery spills or if it is physically damaged it must be replaced stored in a sulfuric acid resistant container and...

Страница 27: ...and in which space is reserved to include them b Batteries installed or planned to be installed partly in the own cabinet of the UPS and the rest in another cabinet or other cabinets or rack c Batteri...

Страница 28: ...do not have it Only in single phase equipments and in compliance with the nominal supply voltage of the equipment it is possible to dispense with the neutral and to replace it with another phase in i...

Страница 29: ...an equipment with protection against class I electrical shock it is essential to install the protec tive earth conductor to the terminal identified as Con nect this conductor before supplying voltage...

Страница 30: ...36 40 or 44 elements con nected in serial but always in even numbers since it is neces sary for the internal architecture of the equipment to have a central point or mid tap N neutral At the same tim...

Страница 31: ...parallel cable is about 1 5 meters and should not be prolonged under any circumstances due to the risk of interferences and failures in the communication that this would entail Fig 28 shows an instal...

Страница 32: ...tical ADAPT X devices Only in 6 slot subracks Cables passed through the decorative side channel in 2 slot and 4 slot sub racks Fig 31 Control cables pass through the inside of the front trim in 2 slot...

Страница 33: ...sales department the T S S or failing this the distributor Tabla 3 Pinout terminal block for temperature probes 5 5 7 3 Signal input of the remote EPO button Emergency Stop The UPS has the EPO functio...

Страница 34: ...ass switch normally open NO the equipment is informed that the switch is in the maintenance position In this condition the supply of the loads will be direct fed from the commercial grid and any anoma...

Страница 35: ...m current applicable to these contacts is 250 V AC 3A J8 J9 J10 _NC _NO GND Fig 39 Terminal block J8 J9 and J10 dry contacts Pin Reference Function J8 1 BYP_ALM_NC Normally closed contact NC dry conta...

Страница 36: ...lied with the user manual defines the protection size their selectivity the number of poles according to the input output configuration and the cross cable section of each line This information is a r...

Страница 37: ...S Red Tab 10 Status indications with inverter running 5 Turn on the protection or circuit breaker of bat teries The red led of the batteries is turned off a few minutes later and then turns green They...

Страница 38: ...separate bypass line 5 Initiate timely maintenance tasks NOTE To remove a faulty module it is not necessary to switch the device to Bypass Mode since a power module can be removed while the system is...

Страница 39: ...RT When the UPS is operating in Normal Mode and the input mains fails it will automatically switch to Batteries Mode where the loads are fed from the inverter from the energy stored in the batteries I...

Страница 40: ...stributor 6 8 1 1 With the system operating in Normal Mode and normal bypass voltage and frequency transfer the load over the manual bypass 1 Manually stop the inverter The UPS will transfer to Bypass...

Страница 41: ...and time Press ENTER to confirm 6 11 LEVEL 1 CONTROL PASSWORD The system is password protected to control unauthorized op erations In section 7 3 5 of the Operation menu the various available functio...

Страница 42: ...ys The EPO push button with the protective cover is avail able on all equipments The BYP INV and MUTE shortcut keys are only avail able in six slot sub racks For further information see Tab 12 NOTE Th...

Страница 43: ...t the system is in a status of general alarm for example when there is an input mains failure Continuous beep Indicates that the system is in a status of urgent alarm for example fuse blown up or syst...

Страница 44: ...mere example Display contents Meaning 40 10 Maximum power system with all installed modules unit power module N 01 1 power module installed in the system S Unit mode S A single unit P 0 1 parallel mod...

Страница 45: ...capacity remaining discharge time discharge times operating days discharge hours battery tem perature and ambient temperature see Fig 48 Fig 48 Cabinet information menu Battery sub menu 7 3 3 Informat...

Страница 46: ...The second the S Code shows the event codes for each power module It is useful for the T S S see Fig 53 Fig 52 Information menu of the module or power modules Information sub menu Fig 53 Information...

Страница 47: ...t connected Connected 22 Battery protection status Open Closed 23 EPO status EPO not activated EPO activated 24 Extracted module Connected Extracted 25 3 INV available INV unavailable Available 26 End...

Страница 48: ...age fault Correct Fault 2 Fan fault Correct Fault 3 Reserved 4 Reserved 5 2 Positive bus undervoltage fault Correct Fault 6 Negative bus undervoltage fault Correct Fault 7 Positive battery reserved Co...

Страница 49: ...served 18 Output short circuit Correct Fault 19 Battery test None Correct Fault 20 Battery maintenance None Correct Fault 21 2 Reserved 22 Reserved 23 Reserved 24 Reserved 25 3 Reserved 26 Reserved 27...

Страница 50: ...put voltage settings Output voltage adjustment from 210 to 230 V Bypass voltage upper margin for Bypass available Upper adjustment Bypass voltage range 10 15 20 or 25 default to 20 Bypass voltage lowe...

Страница 51: ...manual transfer of static bypass 42 Battery low voltage 43 Wrong battery polarity 44 Inverter protection 45 Input neutral fault 46 Bypass fan fault 47 Manual shutdown 48 Manual quick charge 49 Manual...

Страница 52: ...Detail of the functionality of each icon Battery test command The UPS switches to bat tery mode the mains indicator LED is off and the bat tery LED flashes green If the battery is not correct or fails...

Страница 53: ...scilloscope menu Tap on the menu screen to view the waveform of the output voltage and current and the bypass voltage 220 2 220 0 220 1 Fig 58 Oscilloscope menu EMi3 SERVOMOTOR VOLTAGE STABILISER USER...

Страница 54: ...communica tion Cover fixing screws Cover for communication connections Slot cover Fixing screws of the slot cover SNMP Slot behind the cover Fig 59 Slot for SNMP in sub rack of 2 and 4 slots for power...

Страница 55: ...ase of a hy pothetical fault 9 1 2 Exclusions Our company will not be bound by the warranty if it notices that the defect in the product does not exist or was caused by improper use negligence imprope...

Страница 56: ...e distance dB 56 0 power module Operating altitude m 2400 Relative humidity 0 95 non condensing Operating temperature C 0 40 battery life is reduced by 50 for every 10 C increase over 20 C Storage and...

Страница 57: ...le V floating 1 Current ripple C10 5 Boost charge load voltage V cell VRLA 2 4 V cell selectable from 2 30 2 45 V cell Mode of charging to current and constant voltage End of discharge voltage V cell...

Страница 58: ...10 min 130 for 5 min 150 1 for 1 min 150 for 300 ms Superior bypass line protection Circuit breaker 125 of rated output current IEC60947 2 C characteristic Rated current of neutral line A 1 7 In Frequ...

Страница 59: ...59 EMi3 SERVOMOTOR VOLTAGE STABILISER USER S MANUAL...

Страница 60: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: