4.2. DEFINITION OF THE PRODUCT.
4.2.1. Subrack and battery module nomenclatures.
SLC-4+1/6-ADAPT 60X R P2LBDCS B1 380V 60Hz WCO EE666502
M BAT ADAPT 0/2x40AB147/213 100A BC WCO EE666502
EE*
Particular customer specifications.
CO
“Made in Spain” marking in UPS and packaging (for customs).
W
Neutral marking equipment.
60Hz Frequency of the equipment. Skip for 50 Hz.
380V Input-output voltage. Skip for three-phase N
(phase-to-phase voltage) or single-phase 230V (phase-
to-neutral) equipment.
B1
Equipment with external batteries.
S
Ambient temperature probe.
C
Subrack assembled over battery box module.
D
Transient voltage surge supressor.
B
Separate bypass line.
Input-output configuration, three-phase-three-phase.
L
Input-output configuration, single-phase-single-phase.
M
Input-output configuration, single-phase-three-phase.
N
Input-output configuration, three-phase-single-phase.
2
Parallel subrack number.
P
Parallel kit (material needed for parallel subracks).
R
In subrack format (not integrated inside cabinet).
X
Sub-family of the ADAPT series
(2U modules)
60
Maximum installed capacity in subrack in kVA.
ADAPT UPS Series.
6
Maximum number of installable modules in subrack.
+1
Redundant modules.
4
Number of modules installed from factory.
SLC
Acronym abbreviation brand.
CF
50/60 or 60/50 Hz frequency converter
(
1
)
.
EE*
Particular customer specifications.
CO
“Made in Spain” Marking in UPS and packaging (for customs).
W
Neutral mark equipment.
BC
Common battery set (parallel subracks).
100A Protection size.
213
Three last digits of the type-2 battery code.
147
Three last digits of the type-1 battery code.
AB
Initials of the battery family.
40
Number of batteries in each string.
2x
Number of parallel battery strings.
0/
Cabinet batteries without them, with the necessary ac-
cessories to install them.
ADAPT UPS Series.
M BAT Battery module.
(B1)
The equipment is supplied without batteries and without the accessories (screws and electric cables). Predictably the batteries
will be installed in an external cabinet or rack. On request, the cabinet or rack and the necessary accessories can be supplied.
For an equipment ordered without batteries, their acquisition, installation and connection will always be borne by the customer
and
under their responsibility
. However, our
T.S.S.
may be required to intervene in order to carry out the necessary instal-
lation and connection work.
The data concerning the batteries in terms of quantity, capacity and voltage are indicated on the battery label affixed to the side
of the equipment nameplate,
strictly observe
these data and the connection polarity of the batteries.
For equipments with separate static bypass line, an isolation transformer must be installed between any of the two power lines
of the UPS (rectifier input or static bypass), to avoid the direct connection of the neutral of the two lines through the internal