126 - 144
Technical Data Appendix A
A.3 Electric power network specification
Voltage
AC 3PH 380(-15%)~440(+10%)
Short-circuit capacity
Maximum allowed prospective short-circuit current at the input power connection
as defined in IEC 60439-1 is 100 kA. The drive is suitable for use in a circuit
capable of delivering not more than 100 kA at the drive maximum rated voltage.
Frequency
50/60 Hz ± 5%, maximum rate of change 20%/s
A.4 Motor connection data
Motor type
Asynchronous inductance motor
Voltage
0 to U1, 3-phase symmetrical, Umax at the field weakening point
Short-circuit protection
The motor output is short-circuit proof by IEC 61800-5-1
Frequency 0...400
Hz
Frequency resolution
0.01 Hz
Current
Refer to Ratings
Power limit
1.5 · PN
Field weakening point
10...400 Hz
Carrier frequency
4, 8, 12 or 15 kHz
A.4.1 EMC compatibility and motor cable length
To comply with the European EMC Directive (standard IEC/EN 61800-3), use the following maximum motor
cable lengths for 4 kHz switching frequency.
All frame sizes
Maximum motor cable length, 4 kHz
Second environment
(category C3)
30 m without additional output filters
Maximum motor cable length is determined by the drive’s operational factors.
A.5 Applicable standards
The inverter complies with the following standards:
EN ISO 13849-1: 2008
Safety of machinery-safety related parts of control systems - Part 1: general
principles for design
IEC/EN 60204-1:2006
Safety of machinery.
Electrical equipment of machines. Part 1: General
requirements.
IEC/EN 62061: 2005
Safety of machinery – Functional safety of safety-related electrical,
electronic and programmable electronic control systems
IEC/EN 61800-3:2004
Adjustable speed electrical power drives systems. Part 3: EMC
requirements and specific test methods
IEC/EN 61800-5-1:2007
Adjustable speed electrical power drive systems – Part 5-1: Safety
requirements – Electrical, thermal and energy
IEC/EN 61800-5-2:2007
Adjustable speed electrical power drive systems – Part 5-2: Safety
requirements. Functional.
A.5.1 CE marking
The CE mark is attached to the drive to verify that the drive follows the provisions of the European Low
Voltage (2006/95/EC) and EMC Directives (2004/108/EC).
A.5.2 Compliance with the European EMC Directive
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within
the European Union. The EMC product standard (EN 61800-3:2004) covers requirements stated for drives.
See section EMC regulations
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...