Communication Protocol
121
-
144
Code
Name
Meaning
error
is incorrect or the counting of CRC check bit in RTU is different from the lower
monitor.
07H
Written not
allowed.
It only happen in write command, the reason maybe:
1. The written data exceeds the parameter range.
2. The parameter should not be modified now.
3. The terminal has already been used.
08H
The parameter
can not be
changed
during running
The modified parameter in the writing of the upper monitor can not be modified
during running.
09H
Password
protection
When the upper monitor is writing or reading and the user password is set
without password unlocking, it will report that the system is locked.
The slave uses functional code fields and fault addresses to indicate it is a normal response or some error
occurs (named as objection response). For normal responses, the slave shows corresponding function codes,
digital address or sub-function codes as the response. For objection responses, the slave returns a code
which equals the normal code, but the first byte is logic 1.
For example: when the master sends a message to the slave, requiring it to read a group of address data of
the inverter function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it will return:
1 0 0 0 0 0 1 1 (Hex 83H)
Besides the function codes modification for the objection fault, the slave will respond a byte of abnormal code
which defines the error reason.
When the master receives the response for the objection, in a typical processing, it will send the message
again or modify the corresponding order.
For example, set the “running command channel” of the inverter (P00.01, parameter address is 0001H) with
the address of 01H to 03, the command is as following:
But the setting range of “running command channel” is 0~2, if it is set to 3, because the number is beyond the
range, the inverter will return fault response message as below:
Abnormal response code 86H means the abnormal response to writing command 06H; the fault code is 04H.
In the table above, its name is operation failed and its meaning is that the parameter setting in parameter
writing is invalid. For example, the function input terminal can not be set repeatedly.
9.6 Example of writing and reading
Refer to 10.4.1 and 10.4.2 for the command format.
9.6.1 Example of reading command 03H
Read the state word 1 of the inverter with the address of 01H (refer to table 1). From the table 1, the parameter
address of the state word 1 of the inverter is 2100H.
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...