Function Parameters
53
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3: 3-wire control 2
. SIn is the enabling terminal on this
mode, and the running command is caused by SB1 or SB3
and both of them control the running direction. NC SB2
generates the stop command.
Sln
FWD
REV
Direction
ON
OFF
→
ON
ON
Forward
OFF
Reverse
ON
ON
OFF
→
ON
Forward
OFF
Reverse
ON
→
OFF
Decelerate
to stop
Note
:
for the 2-wire running mode, when FWD/REV
terminal is valid, the inverter stop because of the stopping
command from other sources, even the control terminal
FWD/REV keeps valid; the inverter won
’
t work when the
stopping command is canceled. Only when FWD/REV is
relaunched, the inverter can start again. For example, the
valid STOP/RST stop when PLC signal cycles stop,
fixed-length stop and terminal control (see P07.04).
P05.14
S1 terminal
switching-on
delay time
The function code defines the corresponding delay time of
electrical level of the programmable terminals from
switching on to switching off.
Setting range: 0.000~50.000s
0.000 s
○
P05.15
S1 terminal
switching-off
delay time
0.000 s
○
P05.16
S2 terminal
switching-on
delay time
0.000 s
○
P05.17
S2 terminal
switching-off
delay time
0.000 s
○
P05.18
S3 terminal
switching-on
delay time
0.000 s
○
COM
SB2
SB1
FWD
REV
SIn
SB3
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...