Basic Operation Instruction
95
-
144
Control short vibration
A short vibration period with the same value as the derivation time (Td) means that the derivation time is
strong. Shortening the derivation time (Td) can control the vibration. Setting the derivation time as 0.00 (it
means no derivation control) is useless to control the vibration, so the solution is to decrease the gain.
7.11 Pulse counter
CV50 inverters support pulse counter which can input counting pulse through HDI terminal. Usually, this pulse
counter is used to count length. When the actual length is longer than or equal to the set length, the digital
output terminal can output length arrival pulse signal and the corresponding length will be cleared
automatically.