Communication Protocol
123
-
144
If the response message is as below:
Example 2: set the Max. Output frequency of the inverter with the address of 03H as100Hz.
See the figures behind the radix point, the fieldbus ratio value of the Max. output frequency (P00.03) is 100.
100Hz timed by 100 is 10000 and the corresponding hex is 2710H.
RTU mode:
The command sent by the master:
If the operation is successful, the response may be as below (the same with the command sent by the
master):
ASCII mode:
The command sent to the inverter:
If the response message is as below:
9.6.3 Example of continous writing command 10H
Example 1: make the inverter whose address is 01H run forward at 10Hz. Refer to the instruction of 2000H
and 0001. Set the address of “communication setting frequency” is 2001H and 10Hz corresponds to 03E8H.
See the table below.
Function
instruction
Address
definition
Data meaning instruction
R/W characteristics
Communication
control command
2000H
0001H: forward running
W/R
0002H: reverse running
0003H: forward jogging
0004H: reverse jogging
0005H: stop
0006H: coast to stop (emergency stop)
0007H: fault reset
0008H: jogging stop
The address of
communication
setting
2001H
Communication setting frequency (0~Fmax)unit:
0.01Hz
W/R
2002H
PID given, range (0~1000, 1000 corresponds
to100.0%
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...