74 - 144
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
of stage 4
When S1=S2=S3=S4=OFF, the frequency input manner is
selected via code P00.06 or P00.07. When all S1=S2=S3=S4
terminals aren’t off, it runs at multi-step which takes
precedence of keypad, analog value, high-speed pulse, PLC,
communication frequency input. Select at most 16 stages of
speed via the combination code of S1, S2, S3, and S4.
The start-up and stopping of multi-step running is determined
by function code P00.06, the relationship between
S1,S2,S3,S4 terminals and multi-step speed is as following:
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 OFF OFF OFF OFF OFF OFF OFF OFF
Step 0
1
2
3
4
5
6
7
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 ON ON ON ON ON ON ON ON
Step 8
9
10 11 12 13 14 15
Setting range of P10.(2n,1<n<17): -100.0~100.0 %
Setting range of P10.(2n+1,1<n<17): 0.0~6553.5 s (min)
P10.12
Multi-step
speed 5
0.0 %
○
P10.13
Running time
of stage 5
0.0 s
○
P10.14
Multi-step
speed 6
0.0 %
○
P10.15
Running time
of stage 6
0.0 s
○
P10.16
Multi-step
speed 7
0.0 %
○
P10.17
Running time
of stage 7
0.0 s
○
P10.18
Multi-step
speed 8
0.0 %
○
P10.19
Running time
of stage 8
0.0 s
○
P10.20
Multi-step
speed 9
0.0 %
○
P10.21
Running time
of stage 9
0.0 s
○
P10.22
Multi-step
speed 10
0.0 %
○
P10.23
Running time
of stage 10
0.0 s
○
P10.24
Multi-step
speed 11
0.0 %
○
P10.25
Running time
of stage 11
0.0 s
○
P10.26
Multi-step
speed 12
0.0 %
○
P10.27
Running time
of stage 12
0.0 s
○
P10.28
Multi-step
speed 13
0.0 %
○
P10.29
Running time
of stage 13
0.0 s
○
P10.30
Multi-step
speed 14
0.0 %
○
P10.31
Running time
of stage 14
0.0 s
○
P10.32
Multi-step
speed 15
0.0 %
○
P10.33
Running time
of stage 15
0.0 s
○
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...