Function Parameters
79
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
point communication between the upper monitor and the drive.
Note:
The address of the slave cannot set to 0.
P14.01
Baud Rate
Set the digital transmission speed between the upper
monitor and the inverter.
0:
1200BPS
1:
2400BPS
2:
4800BPS
3:
9600BPS
4:
19200BPS
5:
38400BPS
6:
57600BPS
7:
115200BPS
Note:
The baud rate between the upper monitor and the
inverter must be the same. Otherwise, the communication
is not applied. The bigger the baud rate, the quicker the
communication speed.
4
○
P14.02
Digital bit
checkout setting
The data format between the upper monitor and the inverter
must be the same. Otherwise, the communication is not
applied.
0:
No check (N,8,1) for RTU
1:
Even check (E,8,1) for RTU
2:
Odd check (O,8,1) for RTU
3:
No check (N,8,2) for RTU
4:
Even check (E,8,2) for RTU
5:
Odd check (O,8,2) for RTU
6:
No check (N,7,1) for ASCII
7:
Even check (E,7,1) for ASCII
8:
Odd check (O,7,1) for ASCII
9:
No check (N,7,2) for ASCII
10:
Even check (E,7,2) for ASCII
11:
Odd check (O,7,2) for ASCII
12:
No check (N,8,1) for ASCII
13:
Even check (E,8,1) for ASCII
14:
Odd check (O,8,1) for ASCII
15:
No check (N,8,2) for ASCII
16:
Even check (E,8,2) for ASCII
17:
Odd check (O,8,2) for ASCII
1
○
P14.03
Communica tion
answer delay
0~200 ms
It means the interval time between the interval time when
the drive receive the data and send it to the upper monitor.
If the answer delay is shorter than the system processing
time, then the answer delay time is the system processing
time. If the answer delay is longer than the system
processing time, then after the system deal with the data,
waits until achieving the answer delay time to send the data
to the upper monitor.
5
○
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...