Function Parameters
43
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P02.09
Mutual
inductance of
motor 1
0.1~6553.5mH
Depends
on model
○
P02.10
Non-load
current of
motor 1
0.1~6553.5A
Depends
on model
○
P02.26
Motor 1
overload
protection
selection
0: No protection
1: Common motor
(with low speed compensation).
Because the heat-releasing effect of the common motors
will be weakened, the corresponding electric heat
protection will be adjusted properly. The low speed
compensation characteristic mentioned here means
reducing the threshold of the overload protection of the
motor whose running frequency is below 30Hz.
2: Frequency conversion motor
(without low speed
compensation) Because the heat-releasing effect of the
specific motors won’t be impacted by the rotation speed, it
is not necessary to adjust the protection value during
low-speed running.
2
◎
P02.27
Motor 1 over
load protection
coefficient
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the output current
of the inverter and K is the motor protection coefficient.
So, the bigger the value of K is, the smaller the value of M
is. When M =116%, the fault will be reported after 1 hour,
when M =200%, the fault will be reported after 1 minute,
when M>=400%, the fault will be reported instantly.
Setting range: 20.0%~120.0%
100.0%
○
P02.28
Correction
coefficient of
motor 1 power
Correct the power displaying of motor 1.
Only impact the displaying value other than the control
performance of the inverter.
Setting range: 0.00~3.00
1.00
●
P03 Group Vector control
P03.00
Speed loop
proportional
gain1
The parameters P03.00~P03.05 only apply to vector control
mode. Below the switching frequency 1 (P03.02), the speed
loop PI parameters are: P03.00 and P03.01. Above the
switching frequency 2 (P03.05), the speed loop PI
parameters are: P03.03 and P03.04. PI parameters are
20.0
○
P03.01
Speed loop
integral time1
0.200s
○
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...