98 - 144
Fault Tracking
Fault
code
Fault type
Possible cause
What to do
CE
Communication
error
The baud rate setting is incorrect
Fault occurs to the communication
wiring.
The communication address is
wrong
There is strong interference to the
communication
Set proper baud rate
Check the communication
connection distribution
Set proper communication address
Change or replace the connection
distribution or improve the
anti-interference capability
ItE
Current detection
fault
The connection of the control board
is not good
Some board component is broken
The keypad circuit is abnormal
Check the connector and repatch
Change the board
Change the keypad
tE Autotuning
fault
The motor capacity does not comply
with the inverter capability
The rated parameter of the motor
does not set correctly.
The offset between the parameters
from autotunting and the standard
parameters is huge
Autotune overtime
Change the inverter mode
Set the rated parameter according to
the motor name plate
Empty the motor load and reidentify
Check the motor connection and set
the parameter.
Check if the upper limit frequency is
above 2/3 of the rated frequency.
EEP EEPROM
fault
Error of controlling the write and
read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
PIDE PID feedback fault
PID feedback offline
PID feedback source disappear
Check the PID feedback signal
Check the PID feedback source
bCE Braking
unit
fault
Braking circuit fault or damage to the
braking unit
The external braking resistor is not
enough
Check the braking unit
Select proper braking resistor
ETH1
Grounding
shortcut fault 1
The output of the inverter is short
circuited with the ground
There is fault in the current detection
circuit
The actual motor power sharply
differs from the inverter power.
Check if the connection of the motor
is normal or not
Change the board
Change the main control panel
Set motor parameters correctly
ETH2
Grounding
shortcut fault 2
dEu
Speed deviation
fault
The load is too heavy or stalled
Check the load and ensure it is
normal
Increase the detection time
Check whether the control
parameters are normal
STo
Bad adjustment
fault
The autotune parameter is not right
The inverter is not connected to the
motor
Check the load and ensure it is
normal
Check whether the control
parameter is set properly or not
Increase the bad adjustment
detection time
END
Time reach of
factory setting
The actual running time of the
inverter is above the internal setting
running time
Ask for the supplier and adjust the
setting running time
Содержание CV50-008-4F
Страница 1: ...USER MANUAL INVERTER CONTROLVIT CV50 ...
Страница 2: ......
Страница 84: ...84 144 Function Parameters ...
Страница 101: ...Fault Tracking 101 144 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 102: ...102 144 Fault Tracking 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 131: ...Dimension Drawings Appendix B 131 144 18 5 30kW flange mounting 37 110kW flange mounting 132 200kW flange mounting ...
Страница 142: ... ...
Страница 143: ... ...